Service Manual 71
MPS Inverter SINGLE A
• MPS Inverter systems use high COP DC Compressor that take charge of about 50% of
total capacity and high COP constant speed compressors.
- Minimum operation ( About 12~50% load operation )
: High COP DC Compressor covers 12~50% load, COP of system is higher than DC Inverter only system.
- Standard operation ( About 50~90% load operation )
: High COP DC Compressor covers about 10~40% load and constant speed compressor covers 50% load,
COP of system less inferior or equivalent to DC Inverter only system.
- Maximum operation ( About 90~130% load operation )
: COP of DC Inverter compressor goes down according to frequency . In case of MPS system, DC Inverter
compressor rotates between high COP frequency and constant speed compressor covers rest load. COP
of system is higher than DC Inverter Single system.
→
Seasonal EER of DC Inv MPS is the best.
Heating Capacity Improved
• Using TPS technology, LG multi system
achieved world's best wide range of operation
which is from 12%~120% in cooling mode and
from 12%~138% in heating mode to give quicker
cooling and heating.
• Compared cooling capacity
- Standard heating capacity 120%
- Max heating capacity 138%
Energy Saving Gold Fin
- Outdoor Heat Exchanger fins are coated with anti-
corrosive & hydrophilic layers. It prevents the corro-
sion of heat exchanger. Fins remain as new even
after long time of operation and maintain efficiency
of heat exchanger constant. It also saves power &
maintenance Cost
I + II
I
Operatig
Range
24k/30k/36k Grade
18k grade
Compressor
Application
+
Inverter only
Inverter
+Constant
Inverter
+Constant
+Constant
I + II + III
48k/60k Grade
+
I
II
Load
Inverter
compressor
operation
Inverter
compressor
operation
Inverter
compressor
operation
small
large
Constant
Compressor
operation
Constant
Compressor
operation
Constant
Compressor
operation
III
+
+
(
❇
18k means 18,000 Btu/h)
Capacity Control
Heating
Cooling
Before Now
Befor Now
100%
112%
120%~115%
124%
138%~133%
110%
120%
STD
Max
100%
100%
Uncoated Aluminum
Gold fin
10mm
10mm
10mm
10mm
Salt Spray Test Result : After 360 hours
[ Test Standard: ASTM B-117, KS D 9502 ]
Pitting Corrosion
Содержание ABNH186HLAB
Страница 66: ...66 Universal System Air Conditioner II Outdoor Units Introduction 67 AUUW B AUUW 0 R410A 69 ...
Страница 80: ...80 Universal System Air Conditioner MPS Inverter SINGLE A 4 Wiring Diagrams AUUW126B UU12 WUEB ...
Страница 120: ...Electronic Control Device 120 Universal System Air Conditioner Main P C B ASM A 6871A10209 B 58 Ceiling Cacsette Type ...
Страница 121: ...Electronic Control Device Service Manual 121 Ceiling Duct Type BH Series ...
Страница 122: ...Electronic Control Device 122 Universal System Air Conditioner BG BR Series ...
Страница 123: ...Electronic Control Device Service Manual 123 VE Series Ceiling Floor ...
Страница 124: ...Electronic Control Device 124 Universal System Air Conditioner VB Series ...
Страница 125: ...Service Manual 125 V Schematic Diagram Ceiling Cacsette Type 126 Ceiling Duct Type 127 Celing Floor 128 ...
Страница 126: ...Schematic Diagram 126 Universal System Air Conditioner Ceiling Cassette Type ...
Страница 127: ...Schematic Diagram Service Manual 127 Ceiling Duct Type ...
Страница 128: ...Schematic Diagram 128 Universal System Air Conditioner Ceiling Floor ...
Страница 180: ...Exploded View Replacement Parts List 180 Universal System Air Conditioner 152312 135314 137211 268712 146811 PT HFA C ...
Страница 181: ...Exploded View Replacement Parts List Service Manual 181 152312 135314 146811 137211 268712 135802 PT HDA C ...
Страница 183: ...P No 3828A22009B Printed in Korea ...