Outdoor Units
2.5 Sump heating control
2.5.1 Inverter compressor sump heating fuction
: A function protecting inverter compressor from damages, by increasing oil viscosity in low outdoor
temperature.
For the control,compressor operates in low frequencies.
Operating condition :in case of the following 3 conditions are fulfilled at the same time.
- Outdoor temperature, D-pipe temperature, Heat sink temperature : below 0°C,
2.5.2 Constant compressor sump heater (option)
: An optional function protecting constant compressor from damages, by increasing oil viscosity in low outdoor
Temperature.
For this function, heater operates before compressor starting.
Operating condition : before the starting of compressor
outdoor temperature : below 0°C
➨
heater ON, over 3°C
➨
heater OFF
Comp.
Opening target : 0.7
LEV
0 sec.
90~300 sec.
Time (option)
15Hz
starting
starting
OD temp. < 0 ~ -10
°
C
Содержание ABNH186HLAB
Страница 66: ...66 Universal System Air Conditioner II Outdoor Units Introduction 67 AUUW B AUUW 0 R410A 69 ...
Страница 80: ...80 Universal System Air Conditioner MPS Inverter SINGLE A 4 Wiring Diagrams AUUW126B UU12 WUEB ...
Страница 120: ...Electronic Control Device 120 Universal System Air Conditioner Main P C B ASM A 6871A10209 B 58 Ceiling Cacsette Type ...
Страница 121: ...Electronic Control Device Service Manual 121 Ceiling Duct Type BH Series ...
Страница 122: ...Electronic Control Device 122 Universal System Air Conditioner BG BR Series ...
Страница 123: ...Electronic Control Device Service Manual 123 VE Series Ceiling Floor ...
Страница 124: ...Electronic Control Device 124 Universal System Air Conditioner VB Series ...
Страница 125: ...Service Manual 125 V Schematic Diagram Ceiling Cacsette Type 126 Ceiling Duct Type 127 Celing Floor 128 ...
Страница 126: ...Schematic Diagram 126 Universal System Air Conditioner Ceiling Cassette Type ...
Страница 127: ...Schematic Diagram Service Manual 127 Ceiling Duct Type ...
Страница 128: ...Schematic Diagram 128 Universal System Air Conditioner Ceiling Floor ...
Страница 180: ...Exploded View Replacement Parts List 180 Universal System Air Conditioner 152312 135314 137211 268712 146811 PT HFA C ...
Страница 181: ...Exploded View Replacement Parts List Service Manual 181 152312 135314 146811 137211 268712 135802 PT HDA C ...
Страница 183: ...P No 3828A22009B Printed in Korea ...