Installation
70 Universal System Air Conditioner
7. Drain Pipe Work
❑
Drain pipe gradient and support
1) - The drain pipe must be fitted at a gradient of at least 1/100.
- The drain pipe should be as short as possible and free from airlocks.
2) Suspension bolts should be used to support long stretches of drain pipe in order to ensure that a gradient
of 1/100 is maintained.(PVC pipe should not be bent)
Spacing of supports for horizontal piping
3) The length of pipe laid horizontally should be kept a minimum.
Class
Nominal diameter
Spacing
Rigid PVC pipe
25~40mm
1.0m or less
Indoor unit
Gradient of at least 1 / 100
(1cm/ 1m)
■
Drain Piping of Ceiling Cassette
• Drain piping must have down-slope (1/50 to 1/100): be sure not to
provide up-and-down slope to prevent reversal flow.
• During drain piping connection, be careful not to exert extra force
on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor unit is
32mm.
• Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump
operation:
• Connect the main drain pipe to the exterior and
leave it provisionally until the test comes to an end.
• Feed water to the flexible drain hose and check the
piping for leakage.
• Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
• When the test is complete, connect the flexible
drain hose to the drain port on the indoor unit.
Heat insulation material: Polyethylene foam with
thickness more than 8 mm.
Drain test
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
Flexible drain hose
700 or less
1 -1.5m
300mm or less
Clamp metal(attached)
Drain hose(attached)
Drain raising pipe
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Flexible drain hose
CAUTION
The supplied flexible drain hose should not be curved,
neither screwed. The curved or screwed hose may
cause a leakage of water.
1/50~1/100
MAX 700mm
Flexible drain hose
Flexible drain hose
■
Install the drain raising pipes at a right angle to the
indoor unit and no more than 300mm from the unit.
Содержание ABNC186HLAA
Страница 79: ...Electronic Control Device Service Manual 79 Ceiling Duct Type ...
Страница 80: ...Electronic Control Device 80 Universal System Air Conditioner Ceiling Floor ...
Страница 81: ...Schematic Diagram Service Manual 81 Ceiling Cassette Type Schematic Diagram ...
Страница 83: ...Schematic Diagram Service Manual 83 Ceiling Duct Type BH BE Series ...
Страница 84: ...Schematic Diagram 84 Universal System Air Conditioner Ceiling Floor RY 4WAY RY OUTFAN ...
Страница 119: ...P No 3828A22009A Printed in Korea ...