- 9 -
Troubleshooting Guide
1. Error indicator
• The function is to self-diagnosis air conditioner and express the troubles if there is any trouble.
• Error mark is displayed on wired-remote controller and LED of outdoor unit control board.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
•
After error occurs, if error is released, error LED is also released simultaneously.
❈
Indoor Error
Error Code
1
Air sensor (open/short)
Open / Short
Off
2
Inlet pipe sensor
Open / Short
Off
3
Communication(Indoor
↔
Wired R/Control)
Communication Poorly
Off
4
Drain pump/ Float switch
Float switch Open
Off
5
Communication(Indoor
↔
Outdoor)
Communication Poorly
Off
6
Outlet pipe sensor
Open / Short
Off
7
Different mode operation
Different mode operation
Off
9
EEPROM check sum
Check sum mismatching
Off
10
BLDC motor fan lock
Motor not operation
Off
15
Communication(indoor
↔
Fan)
Communication Poorly
Off
Contents
Indoor Status
Case of error
❈
Outdoor Error
Error Code
24
High Pressure Switch operation
High P/S operates 5times for1hour
Off
33
D-Pipe Temp. High
D-Pipe Temp
≥
120°C
Off
44
Air Sensor(open/short)
Open/Short
Off
45
Outlet Pipe Sensor(open/short)
Open/Short
Off
47
D-Pipe Sensor(open/short)
Open/Short
Off
48
S-Pipe Sensor(open/short)
Open/Short
Off
51
Excess Capacity
Indoor load excesses 120K
Off
54
Phase error
Continually 5times error
Off
Contents
Indoor Status
Case of error
Содержание AB-H1208VA0
Страница 1: ...LG Large Duct Type Air Conditioner SERVICE MANUAL MODELS AB H1208VA0 ...
Страница 24: ... 24 Features of Controller 1 Circuit Diagram of Indoor PCB ...
Страница 25: ... 25 2 Circuit Diagram of BLDC Driver ...
Страница 26: ... 26 3 Circuit Diagram of Outdoor PCB ...
Страница 32: ...P No 3828A20845A June 2006 Printed in Korea ...