- 14 -
Troubleshooting Guide
VOLTAGE LIMITS
1. No cooling and heating operation performed
1) Both the blower and the compressor do not work
NAME PLATE RATING
MINIMUM
MAXIMUM
380 - 415 V
342 V
456 V
2) Only Indoor blowers do not work
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Other parts except the
unit
Magnetic switch for com-
pressor & fan motor
Operating switch
• Electric supply interrupted
• Defective power wiring
• Cut off power fuse
Too low voltage
Control point is on condi-
tion of "OFF" due to trou-
ble.
Troubled or defective
contactor
Measure power sypply
with a tester in case that
the same power source is
supplied to other equip-
ment except the unit,
what and where troubled
can be discovered by
checking the operation of
other equipment.
Measure it with a tester.
Make short-circuit, then
measure it with tester.
Check it with the eyes or
tester.
• Repair a switch box and
relative instrument.
• Replacement of fuse
• Request a power
supplier to repair.
Check the power source.
Use a thick cable if nec-
essary.
Replace it if necessary.
Repair or replace it.
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Motor
Reactor
Electric wiring
• Over heated
• Wiring short
Defected
• Cut- OFF of wiring
• Short circuited on
operation
Check it with tester
Check it with a tester.
Check it with a tester.
Repair or replace it.
Replace it.
Rewiring or Repair.
Содержание AB-H1208VA0
Страница 1: ...LG Large Duct Type Air Conditioner SERVICE MANUAL MODELS AB H1208VA0 ...
Страница 24: ... 24 Features of Controller 1 Circuit Diagram of Indoor PCB ...
Страница 25: ... 25 2 Circuit Diagram of BLDC Driver ...
Страница 26: ... 26 3 Circuit Diagram of Outdoor PCB ...
Страница 32: ...P No 3828A20845A June 2006 Printed in Korea ...