INSTALLATION OF INDOOR, OUTDOOR UNIT
ENGLISH
Piping length and elevation
Multiple Piping Models
(Unit: m)
Distributor type Models
(Unit: m)
h2
h1
h1
A
A
B
ranch Pipe
Main Pipe
Distributor
Distributor
B
B
h2
Multiple Piping Type
Distributor Type
Capacity is based on standard length and maximum allowance length is on the basis of relia-
bility. If outdoor unit is at higher elevation than the indoor units, after 24m of vertical height,
1 oil trap is required.
CAUTION
!
18 30 25 15 7,5
26 60 25 15 7,5
30 70 25 15 7,5
36 75 25 15 7,5
48 85 25 15 7,5
Capacity(kBtu/h)
Total Length
Max Length(A/B)
Max Elevation
(h1)
In - In Elevation
(h2)
40 135 55 80 15 30 15
48 145 55 90 15 30 15
54 145 55 90 15 30 15
Capacity
(kBtu/h)
Total Length
Max Main Pipe
Length (A/B)
Total Branch
Pipe Length
Max Branch
Pipe Length
Max Elevation
(h1)
In - In Elevation
(h2)