Part 5. Trouble Shooting
Display
code
Title
Cause of error
Check point & Normal condition
22
AC Input current is higher
than the limit.
• Input voltage error(low
voltage)
• Over load operation
(Outdoor fan constraint,
screened, blocked)
• Burned parts inside PCB
• Check input voltage
• Check outdoor fan canstraint / screened / flow
structure
• Check PCB current sensor parts
5V_GND