Operation
46
300750767_002_C3 - 12/2020 - © Leybold
Controlling the Speed through a Voltage Input
Set parameter b1-01 to 1 (0 default). Through this, the analogue input termi-
nal becomes the main frequency reference.
Set DIP switch S1 to the bottom position V (voltage).
DIP switch S4 must remain at its default position: top, multifunction input.
Set parameter H3-09 to 0. Through this, the input signal type is set to “0-10
VDC with lower limit”. Make sure that parameter H3-10 has been set to the
default value 0.
Connect the control voltage to terminals X103-9 and X103-10. 0 to 10 V,
0 V corresponds to 0 Hz, 10 V corresponds to 110/125/250 Hz
for DV 200/300/500, linear increase.
Controlling the Speed through a Current Input
Set parameter b1-01 to 1 (0 default). Through this, the analogue input termi-
nal becomes the main frequency reference.
DIP switch S1 must be at its default position: top, position I.
DIP switch S4 must be at its default position: top, multifunction input.
Parameter H3-09 must be at its default value 2, input signal type “4-20 mA”).
Make sure that parameter H3-10 has been set to the default value 0.
Connect the control current to terminals X103-9 and X103-10. 4 to 20 mA,
4 mA corresponds to 0 Hz, 20 mA corresponds to 110/125/250 Hz for DV
200/300/500, linear increase.
4.4.3 Warning and Shut-off Thresholds
Designation
Warning
threshold
Shutoff
threshold
Processing by
Fault display
Exhaust pressure (Pressure diffe-
rence to ambient pressure)
PS-1
250 +/- 50 mbar
frequency converter
EF2
Purge gas supply pressure
PS-2
—
2.2 bar(g)
customer PLC
—
Temperature pump motor side
(temperature sensor Pt 1000)
SS-1 SS-2
90 °C
100 °C
frequency converter
100A1 /
100FT
Temperature motor
SS-3
—
70 °C
frequency converter
EF3
Frequency converter temperature
SS-4
105 °C
110 °C
frequency converter
oH
oHi
Fig. 4.5 Changing the speed of the pump
X103
1
8
9
15
2. Frequenz
X103
1
8
9
15
0 - 10 V
4 - 20 mA
Current input
S1 S2 S3 S4 S5 S6 HC SC H1 RP
AC
R+ R– S+ S– IG T1 TC
A2
+V AM AC MP
P1 P2 PC
S3
S1
S4
S2
DIP switch position on the