Installation
32
300750767_002_C3 - 12/2020 - © Leybold
Remote Connector
Type: Sub-D 15 pole male
Pin no. Function
Description
Remarks
1
Baseblock Input low active ref. digital ground
must be activated before Run
2
Digital Ground
reference for 1, 3, 4
3
Run / Stop
low active ref. digital ground
4
2nd Speed
low active ref. digital ground
function not activated
contact supplier for details
5
Digital Ground
reference for 1, 3, 4
6
Warning Output Optocoupler output open collector
(supply only through a resistor, max current
10mA)
low active ref. Optocoupler ground
7
Failure Output
Optocoupler output open collector
(supply only through a resistor, max current
10mA)
low active ref. Optocoupler ground
8
Warning/Fail
Common
Optocoupler ground reference for 6, 7
9
Analog Input
4-20mA / 0-10V
ref. Analog ground
function not activated
contact supplier for details
10
Analog Ground
reference for 9, 11, 15
function not activated
contact supplier for details
11
+10V Analogue
Voltage
+10V
ref. Analog ground
function not activated
contact supplier for details
12
Digital Ground
reference for 14, 15
13
N.A.
14
Reset Input
low active ref. digital ground
15
Normal Output
0 /10V output max 10 mA
ref. to analog ground
Communication Modbus RTU Connector
Type: Sub-D 9 pole female
Pin No. Function
1
n.c.
2
n.c.
3
n.c.
4
n.c.
5
Ground
6
n.c.
7
TxD+/ RxD+
8
TxD-/RxD-
9
n.c.
6
5
1
9
X103
X104
1
8
9
15
6
5
1
9
X103
X104
1
8
9
15