GENERAL INSTRUCTION GUIDE

 

EUROTHERM 2204 FM APPROVED LIMIT CONTROLLERS 

                                                                                                                                                                       

 

 

INDUSTRIAL OVENS 

 

CONFIGURING ALARMS: 

 

Press the 

PAGE

 button until you see 

ACCS

 in the upper portion of display and

 LIST

 in the lower portion 

 

Press the 

SCROLL

 button and the display will show

 

CODE

 in the upper portion of the display and 

0

 in 

the lower display. Press the

 UP

 arrow to change the 

0

 to the number 

1

”.

 

 

Press the 

SCROLL

 button and the display will show 

GOTO

 in the upper display and 

OPER

 

in the lower 

display. 

 

Change

 

OPER

 to 

CONF

 by pressing the 

UP

 arrow button. 

 

Press the 

SCROLL

 button and the display will now show

 

CONF

 in the upper display and 

0

 in the 

lower. 

 

Change the 

0

 to a 

2

” 

using the 

UP

 arrow 

 

Press the 

PAGE

 button until you see

 

AL

 

in the upper display and 

CONF

 

in the lower display. 

 

Press the 

SCROLL

 button once and 

AL 1

 will appear in the upper display and 

FSH

 

will appear in the 

lower display use the 

UP

 arrow to change this to the desired alarm type 

FSH

FSL

,

 or 

OFF

 

For alarm 2, press the 

SCROLL

 button again and the upper display will read 

AL 2

 and use the 

UP

 

arrow to change this to the desired alarm type. 

 

Press the 

PAGE

 button until upper display says

 

EXIT

 and lower display says

 

NO

. Change the 

NO

 to 

YES

 instrument will cycle power and reset.

 

 

TO ADJUST THE ALARM HYSTERESIS VALUE: 

Hysteresis 

is the difference between the point at which the alarm switches 

ON

 and the point at which 

it switches 

OFF

. It is used to prevent relay chatter. 

 

Press the

 PAGE

 button twice. The display will show 

AL LIST >

 

 

Press the 

SCROLL

 button twice. The top display will read 

hY >

 and the lower display will show the 

hysteresis value in engineering units. To adjust the hysteresis value, use the 

UP

 or 

DOWN

 button; the 

minimum value is 1. The hysteresis value is common to any configured alarm. 

 

 

 

 

 

 

 

 
 

 

Содержание EUROTHERM 2204FM

Страница 1: ...se devices to meet their own application requirements not limited to but including adjusting set points and setting up alarms If you do not have a manual for your controller or wish to view an online version of it please use the following link http www eurothermonline com search searchwords manuals searchsmall_4920 2204FM The 2204FM is a 1 4 DIN FM approved alarm indicator with two FM Approved for...

Страница 2: ...y reset The alarm can be acknowledged by pressing the PAGE button TO CHANGE ALARM SET POINTS NOTE If set point is shown in the lower display just press the UP and DOWN arrows If it is not shown follow the instructions below Press the PAGE button 1st on the left twice The display will show AL LIST To display the type of alarm that the instrument is set for press the SCROLL button and the alarm type...

Страница 3: ...the SCROLL button once and AL 1 will appear in the upper display and FSH will appear in the lower display use the UP arrow to change this to the desired alarm type FSH FSL or OFF For alarm 2 press the SCROLL button again and the upper display will read AL 2 and use the UP arrow to change this to the desired alarm type Press the PAGE button until upper display says EXIT and lower display says NO Ch...

Страница 4: ...pper display and OPER in the lower display Change OPER to CONF by pressing the UP arrow button Press the SCROLL button and the display will now show CONF in the upper display and 0 in the lower Change the 0 to a 2 using the UP arrow Press the PAGE button until you see INST in the upper display and CONF in the lower display Press the SCROLL button and you will see UNITS in the upper display and F o...

Страница 5: ...ss the SCROLL button until INPT appears in the upper display and the thermocouple type LEWCO Inc typically uses J J TC shows in the lower display Press UP or DOWN arrow until desired thermocouple type is shown Press SCROLL button again the upper display will read RNG L for range low The present value will be shown in the lower display This value can be changed by pressing the UP arrow the maximum ...

Страница 6: ...in the upper display and OPER in the lower display Change OPER to CONF by pressing the UP arrow Press the SCROLL button and the display will now show CONF in the upper display and 0 in the lower Change the 0 to a 2 using the UP arrow Press the PAGE button until you see IP in the upper display and CONF in the lower display Press the SCROLL button until you see rnG H appear in the uppder display and...

Отзывы: