GENERAL INSTRUCTION GUIDE

 

EUROTHERM 2204 FM APPROVED LIMIT CONTROLLERS 

                                                                                                                                                                       

 

 

INDUSTRIAL OVENS 

 

ALARMS: 

There are 2 FM approved alarm relays available in the 2204i, however some devices may not be configured for 
both alarms. The type of alarm is also configured upon installation and cannot be changed without logging into 
the configuration mode. There are 3 different options for alarm types: 

1. 

FSH

 - Full Scale High 

2. 

FSL

 - Full Scale Low 

3. 

OFF

- this will deactivate the alarm relay 

 

TO ACKNOWLEDGE / RESET THE ALARM RELAY: 

 

The alarm relay is FM approved and must be manually acknowledged. Once the process variable has 

returned to a safe value and the alarm is acknowledged the relays will automatically reset. The alarm 

can be acknowledged by pressing the 

PAGE

 button. 

 

TO CHANGE ALARM SET POINTS:  

NOTE

: If set point is shown in the lower display just press the UP and DOWN arrows. If it is not shown 

follow the instructions below. 

 

Press the 

PAGE

 button (1st on the left) twice. The display will show 

AL LIST >

 

 

To display the type of alarm that the instrument is set for press the 

SCROLL 

button and the alarm type 

will be shown in the upper display.

  NOTE

: If the type of alarm needs to be changed see the section on 

configuring alarms. 

 

The lower display will show the present alarm set point value in engineering units. To change the set 
point value use the 

UP

 or 

DOWN

 button. 

 

NOTE

Set Limit Controller Set Point at 20

°

 F over maximum operating temperature. 

 

Electric Drum Heating Cabinets: 300

°

 F + 20

°

 F = 320

°

 F. 

 

Steam Drum Heating Cabinets: 300

°

 F + 20

°

 F = 320

°

 F. 

 

High Humidity Drum Heating Cabinets: 190

°

 F + 20

°

 F = 210

°

 F. 

 

 

 

 

 

 

Содержание EUROTHERM 2204FM

Страница 1: ...se devices to meet their own application requirements not limited to but including adjusting set points and setting up alarms If you do not have a manual for your controller or wish to view an online version of it please use the following link http www eurothermonline com search searchwords manuals searchsmall_4920 2204FM The 2204FM is a 1 4 DIN FM approved alarm indicator with two FM Approved for...

Страница 2: ...y reset The alarm can be acknowledged by pressing the PAGE button TO CHANGE ALARM SET POINTS NOTE If set point is shown in the lower display just press the UP and DOWN arrows If it is not shown follow the instructions below Press the PAGE button 1st on the left twice The display will show AL LIST To display the type of alarm that the instrument is set for press the SCROLL button and the alarm type...

Страница 3: ...the SCROLL button once and AL 1 will appear in the upper display and FSH will appear in the lower display use the UP arrow to change this to the desired alarm type FSH FSL or OFF For alarm 2 press the SCROLL button again and the upper display will read AL 2 and use the UP arrow to change this to the desired alarm type Press the PAGE button until upper display says EXIT and lower display says NO Ch...

Страница 4: ...pper display and OPER in the lower display Change OPER to CONF by pressing the UP arrow button Press the SCROLL button and the display will now show CONF in the upper display and 0 in the lower Change the 0 to a 2 using the UP arrow Press the PAGE button until you see INST in the upper display and CONF in the lower display Press the SCROLL button and you will see UNITS in the upper display and F o...

Страница 5: ...ss the SCROLL button until INPT appears in the upper display and the thermocouple type LEWCO Inc typically uses J J TC shows in the lower display Press UP or DOWN arrow until desired thermocouple type is shown Press SCROLL button again the upper display will read RNG L for range low The present value will be shown in the lower display This value can be changed by pressing the UP arrow the maximum ...

Страница 6: ...in the upper display and OPER in the lower display Change OPER to CONF by pressing the UP arrow Press the SCROLL button and the display will now show CONF in the upper display and 0 in the lower Change the 0 to a 2 using the UP arrow Press the PAGE button until you see IP in the upper display and CONF in the lower display Press the SCROLL button until you see rnG H appear in the uppder display and...

Отзывы: