2 Installation
4
List of tools and equipment
The installer must have the following tools and equipment before proceeding with the installation:
• an appropriate 15-Amp maximum circuit breaker or a disconnect device
• current/voltage meter
• 4-wire 14 AWG (1.63 mm2) 194°F (90°C) cable
• 3-wire, 14 AWG (1.63 mm2), 194°F (90°C) cable
• small flat-head screwdriver
• #2 Phillips screwdriver
• crimping tool
• wire strippers
• four 1-inch (25 mm) #8 mounting screws suitable for selected mounting surface
2.1 Mounting the VerifEye Series 8000 PT module
WARNING:
•
HIGH VOLTAGE: RISK OF ELECTROCUTION, SHOCK, EXPLOSION, OR ARC FLASH.
To be installed by electrician or other qualified personnel only.
•
TO AVOID FIRE, SHOCK OR DEATH,
turn off all power supplying equipment before
working on or inside the equipment. Use a properly rated voltage sensing device to confirm
power is off.
•
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
In all installations, the VerifEye Series 8000 PT Module must be connected to the source panel voltage
through a 15A maximum disconnect or breaker that disconnects all line and neutral wires, so that the
PT module can be powered down. The disconnect or breaker must be located within easy reach of the
meter operator, and must be labeled to indicate the VerifEye Series 8000 PT module and meter that it is
connected to. The disconnect or breaker device must meet IEC 60947-1, IEC 60947-3 and/or comply with
the local electrical code.
Figure 2 shows a typical system installation for a three-phase 4-wire 347V wye configuration with the
VerifEye Series 8000 PT module mounted adjacent to the electrical panel and the VerifEye meter.