Closing TCP connection 
Shutting down system debug logger 
 
Test complete 

 
Note in the last section where SUCCESS is indicated.  The failure is due to the password not being correct.  

LCD Console 

The Energy Monitoring Hub has an LCD console and two push buttons labeled “menu” and “select”.  These can be used to 
configure some of the basic features of the Energy Monitoring Hub.  The intended purpose of the console is to configure the 
Energy Monitoring Hub to a point where a computer can communicate with it for further detailed configuration.    

When the Energy Monitoring Hub is running, it will show “AcquiSuite Ready” and the current time alternated with the 
Ethernet IP address.  If you choose to enable the console display of data points, the LCD will also show the selected point 
names and current reading values.  The display will change to the next listed item about once every 10 seconds.  If a data 
point name is longer than will fit on the 16 character wide display, it will be scrolled.  Pressing the select button will cause 
the display to change to the next configured item. Pressing the select button quickly will skip through multiple display 
points.  

Pressing the Menu button will cause the main menu to appear. Once [Main Menu] is shown on the console, the menu button 
will change the menu option, and the select button will take action on the currently displayed option.  Some options provide 
sub menus; others allow you to edit the option value.   The following is a tree display of the main menu and sub menus.  

 

[Main Menu] 

 

TCP/IP Config 

 

 

[TCP/IP Config] 

 

 

IP Address 

 

 

Netmask 

 

 

Gateway 

 

 

DNS Server #1 

 

 

DNS Server #2 

 

 

(previous menu) 

 

Network Status 

 

Dialin 

 

Modbus Status 

 

Upload Data Now 

 

Shutdown 

 

Reboot 

 

(previous menu) 

 

The 

TCP/IP sub menu

 will allow you to configure the Ethernet settings for the Energy Monitoring Hub.  To edit the IP 

settings, use the menu button to change options, and press the select button to edit the option.  Once selected, you will see 
the current value displayed and a blinking square cursor on the first character.  Press the menu button to change the 
character or digit.  Press the select button to use the digit and move the cursor to the right one space.  If you press the select 
button multiple times, the cursor will move right a similar number of spaces, allowing you to skip over characters that may 
be correct based on the previous settings.  When you are finished entering the IP address, select a blank space with the menu 
button, and press select.  Any characters still remaining to the right of the cursor will be eliminated. (ie, if changing 
128.193.100.200 to 10.0.0.1, the new IP address will be several digits shorter than the old one.  

Network Status

:  This option will test the Ethernet connection by attempting to ping the following addresses: localhost, 

Ethernet IP address, gateway, dns1, dns2.  The localhost ping will verify the kernel IP stack is properly initialized.  The 
Ethernet ping will verify the Ethernet card's IP address is set and communicating with the kernel.  The Ethernet ping test 
does not send any packets over the Ethernet cable however.  The gateway ping test will verify that the gateway address 
responds to queries.  This test is the first one that actually sends packets over the Ethernet wire.  The gateway test does not 
verify the IP address of the gateway is correct, or that the gateway is working correctly, it only tests that the address 
specified as a gateway responds to a ping request.  The DNS1 and DNS2 ping tests verify the IP addresses listed for DNS 
servers respond to ping requests.  This test does not verify if the DNS servers can actually resolve DNS names to IP 
addresses.   

For a more complete test, use the connection test web page in the Energy Monitoring Hub diagnostics menu. 

Modbus Status

:  This option will report the number of devices currently detected by the Energy Monitoring Hub.  The 

Shop for Power Metering products online at:

1.800.561.8187

www.

PowerMeterStore

.ca

Содержание Energy Monitoring Hub A8812

Страница 1: ...Energy Monitoring Hub Data Acquisition Server Installation and Operation Manual Model A8812 Shop for Power Metering products online at 1 800 561 8187 www PowerMeterStore ca...

Страница 2: ...tered in any manner Neither the seller nor Leviton shall be liable for any injury loss or damage direct or consequential arising out of the use of or inability to use the equipment This Warranty does...

Страница 3: ...generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this e...

Страница 4: ...Ethernet setup 23 Troubleshooting Ethernet Problems 23 System Options 24 Status 24 Processes 24 Date and Time 24 Universal Time Is Your Friend 24 System logs 25 Firmware Update 25 Diagnostics 26 Host...

Страница 5: ...r temperature humidity etc Pulse output transducers for measuring gas electricity water etc from existing meters and sensors Next choose one or more of the following connection methods For LAN install...

Страница 6: ...at 20 c 10k 47 5k 1 of 47 5k at 20 c 47 5k 100k 1 of 100k at 20 c 100k 10M accuracy unrated Pulse mode intended for use with dry contact outputs consumption rate runtime status Standard and KYZ modes...

Страница 7: ...stallation Step 1 Unpack materials Remove all materials from shipping box and verify all required components are available Step 2 Mount the Energy Monitoring Hub on the wall or other appropriate locat...

Страница 8: ...serve and polarity on the Modbus devices Low Voltage analog pulse and RS485 wiring that enter electrical panels must have a minimum insulation rating that exceeds the voltage inside the panel In addit...

Страница 9: ...a problem Inputs 1 8 in pulse or status mode the LED is on when contacts are closed In analog 4 20mA and 0 10V mode the led blinks quickly 2 Hz to indicate an over range alarm error In 4 20mA mode wh...

Страница 10: ...etween the Energy Monitoring Hub and a single temporary computer such as a laptop primary connection will be dial in or dialout by modem You will need the following information from your network admin...

Страница 11: ...ng Hub to reboot Once the Energy Monitoring Hub has rebooted the new IP address will be displayed on the console If DHCP addressing was specified the server assigned address will be displayed Note if...

Страница 12: ...ck the Properties button B In the network setup dialog there should be a list of items including adapters clients and protocols Locate the item labeled Internet Protocol TCP IP Note If you have multip...

Страница 13: ...additional configuration options on each data point line to specify the details of the analog or pulse input These include the 4 20mA device scale multipliers and engineering units Each 4 20mA or 0 10...

Страница 14: ...ernames specified are not able to be changed or renamed nor can arbitrary usernames be added to the Energy Monitoring Hub Access is only controlled by setting the password for the three existing usern...

Страница 15: ...e Show setup Display links for Device configuration and Advanced configuration for each device Show devinfo Display the communications options including baud rate serial number and firmware version wh...

Страница 16: ...efore the Energy Monitoring Hub will log data for it Low Alarm High Alarm Specify a threshold for the alarm If the data point is recorded below the Low Alarm or above the High Alarm levels at the time...

Страница 17: ...must be specified The default TCP port is 502 on most gateways For local Modbus devices attached to the Energy Monitoring Hub RS485 port use 502 Device Name You must provide a name for the Modbus devi...

Страница 18: ...he page The page will be displayed again however the device name and alarm level fields will allow editing Type in a name for the device in the space provided at the top of the page The name should de...

Страница 19: ...r new configuration You may wish to set any alarm thresholds required or check the console check box for any data points that should be displayed on the LCD console 6 Click the Advanced button in the...

Страница 20: ...ng Hub Options range from once per minute to once per hour All of the selections are even divisions of one hour The Energy Monitoring Hub calculates the next log time by finding the next multiple of t...

Страница 21: ...the device list Modbus RS 485 Debug This feature records Modbus RS485 transaction data in the system debug log file You must click the start log button on the system log files page to record this inf...

Страница 22: ...odbus register point list for the specific Modbus device that will be used Wireless Sensor List The sensor list feature works in conjunction with a number of non Modbus sensors Sensor devices such as...

Страница 23: ...evice that moves traffic from the LAN to the internet The default is 192 168 40 1 If you do not have an internet connection for your LAN or you are using a crossover Ethernet cable leave this field bl...

Страница 24: ...DNS name or IP address of your time server The default time Leviton com can be used if the Energy Monitoring Hub has a connection to the Internet The Energy Monitoring Hub will attempt to synchronize...

Страница 25: ...nel Boot log Startup messages about the Linux operating system startup This log shows what hardware items were detected and initialized Ftp Connection log This log shows a list of files transferred by...

Страница 26: ...stablish an HTTP session with the specified upload server Click the begin test to start this process Information will be printed in black Success responses will be printed in Green failure messages wi...

Страница 27: ...ons and press the select button to edit the option Once selected you will see the current value displayed and a blinking square cursor on the first character Press the menu button to change the charac...

Страница 28: ...nitoring Hub cleanly prior to disconnecting the power from the device The Energy Monitoring Hub has an advanced menu that can be used to perform system checks and clear all configuration options to th...

Страница 29: ...le below 3 Low Range alarm bitmap hex notation 4 High Range alarm bitmap hex notation 5 Data point 1 6 Data point 2 7 8 Data point N Comments Date Time The date time column reports the time at which d...

Страница 30: ...LL are reported as blank fields This makes it easier to import into MS Excel as blank cells With the current firmware the Energy Monitoring Hub will report blank fields rather than NULL to make direct...

Страница 31: ...to send data when an alarm is detected and will upload that information to the LEM website in a timely manner The LEM website will then send email notifications if necessary If this option is disabled...

Страница 32: ...he page For each device a separate log file will be saved Select the device from the dropdown list provided Specify Comma or Tab delimited data and indicate if column headers are required Click the do...

Страница 33: ...ased system access data from any web browser Subscription Based Service Annual Subscription w Declining costs The Best Reports Suite on the market REAL TIME Scalable and versatile for all utilities me...

Страница 34: ...Steps for Microsoft Windows command prompt ftp Use the following commands ftp 192 168 40 50 Use the IP address of your Energy Monitoring Hub username root password admin The same as the admin password...

Страница 35: ...om that requires 2 5 clearance Two 1 2 holes are provided in the bottom of the Energy Monitoring Hub for wiring purposes The Energy Monitoring Hub has 4 mounting holes for use with a 6 or 8 screw The...

Отзывы: