Sender Address:
The address that will be used in the “From:” line of the email. This is helpful in identifying the source of
the alarm email message. If your SMTP mail server has junk filtering, you may be required to use a sender address that
matches a mailbox address on the SMTP mail server; check with your mail server administrator for specific details on this
issue.
Recipient address 1 (2, 3):
The Energy Monitoring Hub can send a copy of the alarm notice to multiple email addresses.
Specify one, two or three email addresses in the fields provided for the recipient addresses.
Modbus Framework
The Modbus Framework feature is a tool to allow the Energy Monitoring Hub to read data from any Modbus device by
creating a template in the Modbus Framework editor. The template describes the Modbus register read commands, and the
conversion required for each data point that is to be read. The Framework feature is an advanced feature of the Energy
Monitoring Hub that requires the user to be familiar with the Modbus protocol and with the Modbus register point list for
the specific Modbus device that will be used.
Wireless
Sensor List
The sensor list feature works in conjunction with a number of non-Modbus sensors. Sensor devices such as PointSix,
BAPI, and Badger/Orion typically transmit data on a pre-set interval and are not polled by the Energy Monitoring Hub.
Data is received and uniquely identified by the sensor's serial number. Each sensor may be given a name, and some have
additional options to configure such as input value scaling.
ModHopper Map
The Energy Monitoring Hub has additional diagnostic features that assist with ModHopper deployments. The most useful is
the ModHopper route map. Select the ModHoppers menu from the Wireless section in the Energy Monitoring Hub menu
tree as shown below.
The graph will draw a blue box for each ModHopper that is attached to the system. The blue number inside the box icon is
the Modbus address of the ModHopper. To the side of each icon, three lines of information will be shown.
The device list name will be shown to the side of each ModHopper icon
The link quality, hops and round trip time (rtt) will be printed under the ModHopper name.