Atlas-X1™ Shielded Connector Termination Instructions
1
Using an appropriate cable stripper, remove about 1.5 inches (38 mm) of cable
jacket. Inspect shield foil and pairs to ensure no foil or insulation damage.
2
At the strip point of the cable, use flush cutters to carefully remove strip string,
if one is present. Spare back the foil metal side outward. Spare back the drain
wire (Figure A). Use flush cutters to remove Mylar
®
tape, cross-shaped pair
separator, or any other cable fillers or spacers.
3
Line up the wire manager with the blue pair indication on the label in line
with the blue pair of the cable. Ensure that the end of the cable jacket is
at the cable jacket stop inside the wire manager, and click the wire manager
closed (Figure B).
4
Observing pair polarity and T568A or T568B wiring pattern, seat the four pairs
into the wire manager.
Note:
Pairs must be completely and securely seated into wire manager wire channels (Figure C).
Figure A
Figure B
Figure C