![Leviton Cat 6A Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/leviton/cat-6a/cat-6a_interactive-reference-manual_1886279017.webp)
CABLE CAPACITY FOR TRAYS AND CONDUIT
CAT 5E
CAT 6
CAT 6A
UTP
UTP
UTP
UTP
UTP with
Isolation Wrap
Shielded
Average OD
0.185 in
(5 mm)
0.23 in
(6 mm)
0.33 in
(8 mm)
0.3 in
(8 mm)
0.275 in
(7 mm)
0.29 in
(7 mm)
Cable Tray
25% 50% 25% 50% 25% 50% 25% 50% 25% 50% 25% 50%
2" x 6"
(51 x 152 mm)
111 222
72
144
35
70
42
84
50
101
45
90
4" x 8"
(102 x 203 mm)
298 596
192 384
93
186
113 226
134 269
121 242
6" x 20"
(152 x 508 mm)
1116 2232 722 1444 350 700
424 848
505 1010 454 908
Conduit
40%
40%
40%
40%
40%
40%
3/4"
(19 mm)
6
5
1
*
1
*
3
2
*
1"
(25 mm)
11
8
3
4
5
4
1 1/4"
(32 mm)
19
14
5
6
8
7
1 1/2"
(38 mm)
25
19
8
10
11
10
*
Conduit Fill Ratio NEC Chapter 9: 1 Cable = 53% maximum fill ratio, 2 cables = 31%, 3 or more = 40%
Cable Tray Fill
TIA-569-D recommends 25% fill at initial installation and
up to 50% with unplanned additions. If a single cable tray
will also carry power cables, a physical barrier is required to
comply with the NEC and IEC. Finally, ensure tray support
spacing is sufficient to prevent excessive sagging. Consider
solid bottom tray for higher density applications.
Note: A tray at 25% fill looks half-full. A tray at 50% fill looks completely full.
Cable trays should be loaded no more than six inches deep.
Conduit Fill
A maximum conduit fill ratio of 40% is recommended by
TIA-569 standards to accommodate cable bundle bend
radius requirements and allow for future expansion.
Pathways and Spaces
|
(800) 722 2082
|
+1 (425) 486 2222
|
17
Installation > Pathways and Spaces >
Cable Tray Fill and Conduit Fill
Testing
Product
Overview
Termination
Cat 6A
Glossary and
References
Installation