Current transformers may not be installed in an area where they block ventilation openings.
•
Current transformers may not be installed in an area of breaker arc venting.
•
Not suitable for Class 2 wiring method nor intended for connection to Class 2 equipment.
•
Secure current transformer and route conductors so that they do not directly contact live terminals
or bus.
•
External secondary inputs and outputs should be connected to devices meeting the requirements of
IEC 60950
•
The following additional requirements apply for Recognized board versions of the VerifEye meter
•
For use only with Listed Energy-monitoring Current Transformers
•
Associated leads of the current transformers shall be maintained within the same
overall enclosure.
•
Unless the current transformers and its leads have been evaluated for REINFORCED
INSULATION, the leads must be segregated or insulated from different circuits.
•
The current transformers are intended for installation within the same enclosure as the
equipment. These may not be installed within switchgears and panel boards” or similar.
•
Use this device with
copper or copper clad wire only
.
•
For indoor use only.