4 General Metering Features and Functionality
19
•
Screens 14-17 – Real Power Delivered (consumed) kW A, kW B, kW C, kW SUM
- Also
known as Instantaneous Demand. Displayed values correspond to “Phase A Real Power,”
“Phase B Real Power,” “Phase C Real Power,” and “Total Power (A+B+C)” in Modbus Register
Map (see Appendix A).
•
Screens 18-20 – Power Factor (PF)
– Per-phase Power Factor is displayed. A lagging power
factor is indicated by the Energy Flow arrow pointing to the left; for leading power factor arrow
points to the right.
•
Screen 21 – Frequency (HZ)
- Displayed in Hertz.
4.5
Manually Setting the Real Time Clock
Figure 11: SCROLL and Max Demand/Clock Reset Switch on Outdoor Series 3300/3500 Meter
Outdoor Models
Indoor Models
SCROLL
Pushbutton
Max Demand
Reset/RTC
KEYSWITCH shown
in OFF/Normal
1.
Press and hold the SCROLL pushbutton; see Figure 11.
2.
While holding SCROLL, rotate the Max Demand Reset/RTC KEYSWITCH to the right into the
RESET/ON position within 3 seconds and then release it. Date will be displayed and Year
will flash.
3.
Press SCROLL to advance the Year (you may also hold it down to advance automatically). The
Year will cycle from 12 through 99 then back to 12 (for 2012 through 2099).
4.
When the Year is set, rotate the KEYSWITCH to ON again and release. The Month will
now flash.
5. Set the Month (1 to 12).
6. Repeat for Day of the Month (range varies by month and leap-year).
7. The next KEYSWITCH ON/release cycle will show the Time and flash the Hour.
8. Repeat the setting sequence for Hour (0-23), Minutes (0-59) and Seconds (0-59).
9. You may again perform KEYSWITCH ON/Release to cycle back to the Date settings, if desired.
10.
The Date/Time setting mode will end automatically after no user activity for 10 seconds. The
Date/Time settings will be stored and the meter will return to its normal display operation.
Note:
•
The Day of the Week (Sunday through Saturday) is calculated and stored automatically by
the meter.
•
Metering functions and communications are not affected during this Date/Time
setting process.