HTU330-3500…-M12 - 01

2020/08/05

HTU330-6000…-M12 - 01

Device functions and indicators

All settings on the sensor are taught-in via the teach button. Device status and switching states are indicated as follows by means 

of 3 LEDs: 

Switching behavior

Switching behavior with 2-point window-teach as a function of the switching function

1-point teach (1 switching point per output)

Switching behavior NO contact

Switching behavior NC contact

2-point window-teach (2 switching points per output)

Switching behavior NO contact

Switching behavior NC contact

NOTE 

The switching behavior is not defined in the dead zone.

Switching function 

configured as

First taught object 

distance

Second taught object 

distance

Output switching behavior

NO (normally open)

Close

Far

Far

Close

NC (normally closed)

Close

Far

Far

Close

D

ead

 zo

ne

Se

nsor

OUT active

Yellow/blue LED ON

Green LED OFF

OUT not active

Yellow/blue LED OFF

Green LED ON

Distance

Hysteresis

Switching point

Scanning range

OUT not active

Yellow/blue LED

OFF

Green LED OFF

OUT not active

Yellow/blue LED 

OFF

Green LED OFF

De

ad

 zon

e

Sen

sor

OUT not active

Yellow/blue LED OFF

Green LED ON

OUT active

Yellow/blue LED ON

Green LED OFF

Distance

Hysteresis

Switching point

Scanning range

OUT active

Yellow/blue LED

ON

Green LED OFF

OUT active

Yellow/blue LED 

ON

Green LED OFF

D

ea

zone

Senso

r

OUT active

Yellow/blue 

LED ON

Green LED 

OFF

OUT not 

active

Yellow/blue 

LED OFF

Green LED 

ON

Distance

Hysteresis

Scanning range

OUT not active

Yellow/blue LED

OFF

Green LED OFF

OUT not active

Yellow/blue LED 

OFF

Green LED OFF

Hysteresis

OUT not 

active

Yellow/blue 

LED OFF

Green LED 

ON

Switching point 1

Switching

point 2

D

ea

zone

Senso

r

OUT active

Yellow/blue 

LED ON

Green LED 

OFF

OUT not 

active

Yellow/blue 

LED OFF

Green LED 

ON

Distance

Hysteresis

Scanning range

OUT active

Yellow/blue LED

ON

Green LED OFF

OUT active

Yellow/blue LED 

ON

Green LED OFF

Hysteresis

Switching point 1

Switching

point 2

OUT active

Yellow/blue 

LED ON

Green LED 

OFF

HTU330

Содержание HTU330 Series

Страница 1: ... point can be taught NO NC function reversible 2 independent switching outputs PNP or NPN NEW Both outputs can easily be taught using a button NEW Stable plastic design NEW Temperature compensated scanning range 250 3500mm 350 6000mm Accessories available separately Mounting systems Cables with M12 connector KD Dimensioned drawing A Active sensor surface B Teach in button C Indicator diodes DMU330...

Страница 2: ... Plastic PBT Active surface Epoxy resin glass fiber reinforced Weight 140g 170g Ultrasonic transducer Piezoceramic 7 7 The ceramic material of the ultrasonic transducer contains lead zirconium titanate PZT Connection type M12 connector 5 pin Fitting position Any Environmental data Ambient temp operation storage 20 70 C 20 70 C Protective circuit 8 8 1 short circuit and overload protection 2 polari...

Страница 3: ...connector pin 4 black cable wire OUT1 4 PNP output NO contact preset P PNP output NC contact preset 2 NPN output NO contact preset N NPN output NC contact preset Pin assignment of connector pin 2 white cable wire Analog OUT OUT2 4 PNP output NO contact preset P PNP output NC contact preset 2 NPN output NO contact preset N NPN output NC contact preset C Analog output 4 20mA V Analog output 0 10V Pi...

Страница 4: ...LED OFF Green LED ON Distance Hysteresis Switching point Scanning range OUT not active Yellow blue LED OFF Green LED OFF OUT not active Yellow blue LED OFF Green LED OFF Dead zone Sensor OUT not active Yellow blue LED OFF Green LED ON OUT active Yellow blue LED ON Green LED OFF Distance Hysteresis Switching point Scanning range OUT active Yellow blue LED ON Green LED OFF OUT active Yellow blue LED...

Страница 5: ...ior with 2 point window teach as a function of the switching function 1 Place object at desired switching distance 1 First place object at desired switching distance for switching point 1 2 To adjust the selected output press the teach button for 2 7s until the yellow LED OUT 1 or blue LED OUT 2 flashes at 3Hz The current state of the selected output is frozen during the adjustment process 2 To ad...

Страница 6: ...d the switching output is changed to the opposite state toggled First activate the previously described teach mode for output OUT 1 or OUT 2 Changeover of the switching function 1 To change the switching function of the selected output press the teach button for longer than 12s The current state of the selected output is frozen during the adjustment process 2 The green and yellow blue LEDs flash a...

Страница 7: ...gram A synchronization pulse from the control activates synchronous operation The devices work in synchronous operation with a simultaneous transmission pulse The response time of the individual sensors in the network corresponds approximately to that of a single sensor Synchronous operation wiring schematic Timing diagram for synchronous operation Working distance Minimum mounting distance 1 500m...

Страница 8: ...ease the button The green yellow and blue LEDs flash alternately and very quickly for a brief time The sensor was reset to the factory setting switching output OUT 1 NO contact 1 switching point at 3500 mm or 6000 mm static 1 point teach switching output OUT 2 NC contact 1 switching point at 3500 mm or 6000 mm static 1 point teach Sensor 2 Sensor 1 Sensor n NOTE Please make certain that the wiring...

Отзывы: