Product description
Leuze electronic GmbH & Co. KG
CSL 505
17
3.5.15
Overview table of configuration values for receiver
Configuration values
Default value
(value range)
Description
First beam
1
Value is always 1
Last beam
2
xx
Value is dependent on bar
Switching output
(dark/light)
Dark switching
Light switching
Dark switching
Output functions
(pin 2/pin 4)
Antivalent
Normal
Normal with inverted warning output
Swapped
Swapped with inverted warning output
Swapped without warning output
Antivalent
Beam mode
Parallel
Diagonal with Rx polarity
reversal
Parallel
Diagonal
Crossed-beam*
2x crossed beam*
3x crossed beam*
(*only where
Synchronization beam =
last
)
Relative switching
threshold
85
(0…255)
85 corresponds to 33
% (255
corresponds
to 100
%)
0 = Automatic switching threshold setting
active.
Blanking of defective
beams
0
(0…160)
Max. number of defective beams that are
blanked automatically.
Autom. beam bl. delay
[s]
0
(0…255)
Time that must pass before a beam
interruption is blanked. Specified in
seconds.
Automatic beam
blanking
0
(0…160)
Number of consecutive beams of the
same type which can be blanked.
Start beam of second
switching range
0
This beam is the beginning of the 2nd
range.
Recommended for
"parallel" beam mode
only!
Synchronization beam
first
first = Synchronization using first beam.
last = Synchronization using last beam.
Smoothing (range 1)
1
(1…160)
Number of interrupted beams as of which
an interruption is detected.
Smoothing (range 2)
1
(1…160)
Number of interrupted beams as of which
an interruption is detected. (range 2)
Pulse stretching [ms]
0
(0…255)
Time period in ms between output
changes.
(Value range: 0 – 255 ms)
Top blanking
0
(0…160)
Number of consecutive beams which can
be blanked during start-up.
Only where blanking threshold = 0.
Relative switching
threshold: Warn
147
(0…255)
Threshold for soiling warning.
Corresponds to 57
% (value * 256)
2
Only the value of the physically present beams should be set; an incorrect value can lead to malfunctions.