Start-up
Leuze electronic
ROD4… plus
33
TNT
35/7-2
4
V
be defined around the obstacle. Measurement is then performed with the maximum possible
accuracy within this area.
In addition, it is possible to filter the measurement values prior to transfer and, thus, only
transfer measurement values which lie in a freely configurable coordinate range.
Furthermore, instead of individual coordinate values, it is possible to transfer only the
extreme values within the individual measurement segments.
Notice!
The transferred configuration data are stored in the ROD4…plus. They are, however, stored
in volatile memory, i.e. they are lost when the ROD4…plus is switched off.
6.2.3
Defining detection fields with RODsoft
(only ROD4 plus and ROD4-08 plus)
Commissioning procedure:
• Install the
RODsoft
configuration software on the PC (setup.exe)
• Connect the ROD4…plus to the PC via the KB-ROD4 plus… cable
• Use the
Start RODsoft
menu option to start
RODsoft
from within
RODplussoft
• Enter password "
ROD4LE
" in level "authorised customer"
Short description:
The detection field can then be displayed under "Display measurement contour". Under
"ROD4 configuration" the response times, the detection field switches and other parameters
are defined. To configure the detection fields, select the "Define detection areas" field. Error
codes and other information are contained in the ROD4 system data. A detailed description
can be found in the user manual for the
RODsoft
configuration software.
Figure 6.1:
User interface of the
RODsoft
configuration software
Current measurement
values (yellow line)
Far
detection field
(green line)
Near
detection field
(red line)