Electrical connection and commissioning
Before you begin with the installation and commissioning of the
TMC 66 Legacy
, please observe the
following notes:
• Make sure that the system is disconnected from the power supply.
• Make sure that no one is in the danger zone.
• Check the danger zone and take measures to prevent persons from entering (e.g. erect warning
signs, set up cordons or similar).
Step 1: Replace the defective TMC 66 with the MSI 420.TMC-03
The table below shows the wiring for the existing signals.
Table 4.1:
Rewiring TMC66 to MSI 420.TMC-03
NOTE
Laying cables!
Lay all connection cables and signal lines within the electrical installation space or permanently in
cable ducts.
Lay the cables and lines so that they are protected against external damages.
For further information: see EN ISO 13849-2, Table D.4.
TMC66
MSI 420.TMC-03
Designation
Comment
1
T1
SLS activation
2
I1
SLS input
3
I2
Start/activation input
see chapter 3 "Description of func
4
I3
Contactor monitoring input
Only relevant in operating mode 3
and 4
5
IQ1
"Error" signal output
6
IQ2
"Safety on" signal output
7
IQ3
Start 1 active
Muting sensor transmitter
8
I4
Start 1 edge
Muting sensor receiver
9
IQ4
Start 2 active
Muting sensor transmitter
10
I5
Start 2 edge
Muting sensor receiver
11
A1/B1/B2
+ 24 V
12
A2
GND
13
I6
Control 1
14
I7
Control 2
15
Q3
Indicator light 1
Muting lamp not monitored by the
MSI 420.TMC
-
03
16
n.c.
Indicator light 2
MSI 420.TMC-03 provides only one
output for the muting lamp
n.c.
Q4
"Error indication" signal output see chapter 5 "Diagnostics mes
17/18
Q1
Safety output 1
Semiconductor output (PNP)