Description of functions

By means of muting, the protective function of the safety sensor can be temporarily and properly 

suppressed, e.g. if objects are to be transported out of the danger zone through the protective field. The 

OSSDs of the MSI 420.TMC-03 remain in the ON state in spite of interruption of the protective sensor.

3.1

Arrangement of the muting sensors

Muting sensors detect the transport material and supply the signals necessary for muting. Standard 

IEC 62046 provides basic information on arranging the muting sensors. This information must be observed 

when mounting the muting sensors.

Operation of the MSI 420.TMC-03 is described below based on the various phases of the muting process.

3.2

Signals

Table 3.1:

Signals

WARNING

Serious accidents caused by incorrect set-up!
If the distance between transmitter and receiver is larger than the width of the object so that gaps of more 

than 180 mm are created, suitable measures, e.g. through additional guarding, must be taken to stop the 

dangerous movement before persons enter the area.

Make sure that no persons can reach the danger zone alongside the transport material during muting.

Make sure that muting is only temporarily activated and only as long as the access to the danger zone 

is blocked by the transport material.

NOTE
If accessible distances exist between the transport material and the safety sensor, PS mats or wicket 

gates monitored with safety switches have been tried, tested and proven as additional safeguards. Such 

measures prevent injuries caused, for example, by crushing in the access area.

WARNING

Unintentionally triggered muting may result in serious injury!

Mount the muting sensors in such a way that muting cannot be unintentionally triggered by a person, 

e.g. by simultaneously activating the muting sensors with a foot.

Mount the muting indicator so that it is always visible from all sides.

WARNING

Risk of death through inadequate protection of the muting sensors!

Protection against unintended initiation of the (permanent) bridging through mechanical damage and/

or misalignment of muting sensors (acc. to IEC 62046).

Signals at MSI 400

Source

Description

Control 1

Input

E.g. standard PLC 

(source A)

Preparations for muting

Control 2

Input

E.g. motor contactor of 

conveyor belt (source B)

Preparations for muting

Содержание MSI 420.TMC-03

Страница 1: ...TMC 03 TMC 66 Legacy S A F E I M P L E M E N T A T I O N A N D O P E R A T I O N O r i g i n a l o p e r a t i n g i n s t r u c t i o n s 2019 10 08 50143065 We reserve the right to make technical c...

Страница 2: ...ing cases Safety relay is not used as intended Safety notices are not adhered to Reasonably foreseeable misuse is not taken into account Mounting and electrical connection are not properly performed P...

Страница 3: ...tem response time 4 3 Description of functions 5 3 1 Arrangement of the muting sensors 5 3 2 Signals 5 3 3 Muting phases 6 3 4 Override Starting system with occupied protective sensor 9 3 5 Reactivati...

Страница 4: ...MSI 400 hardware manual The German and English version of the manual can be downloaded at our website www leuze com by entering the article number 50142625 Please also refer to the manual for the use...

Страница 5: ...Operating mode 3 Start restart interlock active contactor monitoring active Operating mode 4 Start restart interlock inactive contactor monitoring active The respective operating mode is selected by m...

Страница 6: ...connection and commission ing 2 3 Muting sensors Throughbeam or retro reflective photoelectric sensors with activation input PNP HIGH active can be used as muting senders for the MSI 420 TMC 03 2 4 P...

Страница 7: ...sons enter the area Make sure that no persons can reach the danger zone alongside the transport material during muting Make sure that muting is only temporarily activated and only as long as the acces...

Страница 8: ...them to follow the predefined signal change within the predefined time The muting function is ready as soon as testing of Start 1 and Start 2 has been successfully completed If tR is exceeded muting...

Страница 9: ...5 ms after Start 1 has been interrupted Start 2 is also allowed to be interrupted by the trans port material During this phase the two muting sensors i e both start signals as well as the protective s...

Страница 10: ...ain If an error is de tected during direction monitoring the muting process is terminated and an error message is ac tivated see chapter 5 Diagnostics messages Important If Start 1 and Start 2 come fr...

Страница 11: ...g of an emergency stop muting errors or other similar circumstances If a valid override sequence with a LOW HIGH LOW transition min 350 ms and max 3 s longer or shorter pulses are ignored occurs at in...

Страница 12: ...y the cables and lines so that they are protected against external damages For further information see EN ISO 13849 2 Table D 4 TMC66 MSI 420 TMC 03 Designation Comment 1 T1 SLS activation 2 I1 SLS in...

Страница 13: ...a competent person If for example operating mode 3 has been 19 20 Q2 Safety output 2 Semiconductor output PNP n c I10 Selection of operating mode see table 4 2 Selection of operat ing mode n c I11 Se...

Страница 14: ...art inter lock In the operating mode with start restart interlock the MSI 420 TMC 03 expects two signal changes as the switch on signal sensor function A fault in the start button e g caused by welded...

Страница 15: ...es in the immediate surround ings e g safety guard properly mounted and secured against tampering If it is possible to be present undetected between the safety sensor and point of operation is an assi...

Страница 16: ...safety control the safety functions undergo a complete check Has the protective function been checked in accordance with the testing instructions given in this documentation In particular a Function...

Страница 17: ...on on the specific error Table 5 1 Diagnostics messages Safety on IQ2 Error IQ1 Error indication Q4 Status Measures Active Inactive Inactive Normal opera tion None Inactive Active Active 1x every 5 se...

Страница 18: ...ons who have been instructed to do so If changes have been made to the machine or protective device or the safety control has been modified or repaired then check the system again according to the che...

Страница 19: ...Leuze electronic MSI 420 TMC 03 17 8 EU EC Declaration of Conformity...

Страница 20: ...Leuze electronic MSI 420 TMC 03 18...

Отзывы: