Leuze electronic MSI 420.TMC-03 Скачать руководство пользователя страница 14

Leuze electronic

MSI 420.TMC-03

12

selected, it must be checked whether both the start/restart interlock and the contactor monitoring are active 

in the application.

Table 4.2:

Selection of operating mode

Step 3: Check alignment of muting sensors and protective sensor
Before the supply voltage is applied for the first time, it should be checked whether the muting sensors and 

the protective sensor are aligned in accordance with the product-specific operating instructions and not 

concealed by other objects. 
Step 4: Apply supply voltage
Switch on the supply voltage of the MSI 420.TMC-03 and wait until the control has performed the self test 

(approx. 5 seconds). The following indicators now light up on the front of the MSI 400:

PWR/EC LED: green
The voltage supply is between 16.8 V and 30 V.

MS LED: green
The control is started.

CV LED: orange
The project on the control has been verified. The control will start automatically.

If the device is not in this state, table 5.1 „Diagnostics messages“ in this document or the operating instruc

-

tions supplied with MSI 420 (chapter 3.2 "Interfaces and display elements") can be used for the purpose 

of error diagnosis.
Step 5: Make ready for operation
The start/activation input (I2) functions in two ways in the operating modes with/without start/restart inter

-

lock: 

• In the operating mode with start/restart interlock, the MSI 420.TMC-03 expects two signal changes 

as the switch-on signal (sensor function). A fault in the start button, e.g. caused by welded contacts, 

is reliably detected by the MSI 420.TMC-03. 

• In the operating mode without start/restart interlock, the input functions as an activation input and 

must be supplied with power via the 24 V voltage supply. As soon as a HIGH active signal is present 

at I2 and the protective field is free, the safety outputs are closed.

Step 7: Check operation of MSI 420.TMC-03
After successful commissioning, operation of the device can be fully tested. To do this, proceed as follows:

• Interrupt the protective sensor; the safety outputs Q1/Q2 must change their status display. From 

green (active) to red (inactive). The downstream contactors are switched off and the dangerous 

movement is stopped.

• Align the muting sensors (inputs I4/I5 must be green/active)
• Connect the two control inputs (I6/I7 must be green/active)
• Allow the transport material to pass through the protective sensors as described in chapter 3.3.

MSI 420.TMC-03

Selection

Operating mode 1

Start/restart interlock active, con

-

tactor monitoring inactive

I10 (n.c), I11 (n.c), I12 (n.c)

Operating mode 2

Start/restart interlock inactive, 

contactor monitoring inactive

I10 ->24V

Operating mode 3

Start/restart interlock active, con

-

tactor monitoring active 

I11 ->24V

Operating mode 4

Start/restart interlock inactive, 

contactor monitoring active

I12 ->24V

Содержание MSI 420.TMC-03

Страница 1: ...TMC 03 TMC 66 Legacy S A F E I M P L E M E N T A T I O N A N D O P E R A T I O N O r i g i n a l o p e r a t i n g i n s t r u c t i o n s 2019 10 08 50143065 We reserve the right to make technical c...

Страница 2: ...ing cases Safety relay is not used as intended Safety notices are not adhered to Reasonably foreseeable misuse is not taken into account Mounting and electrical connection are not properly performed P...

Страница 3: ...tem response time 4 3 Description of functions 5 3 1 Arrangement of the muting sensors 5 3 2 Signals 5 3 3 Muting phases 6 3 4 Override Starting system with occupied protective sensor 9 3 5 Reactivati...

Страница 4: ...MSI 400 hardware manual The German and English version of the manual can be downloaded at our website www leuze com by entering the article number 50142625 Please also refer to the manual for the use...

Страница 5: ...Operating mode 3 Start restart interlock active contactor monitoring active Operating mode 4 Start restart interlock inactive contactor monitoring active The respective operating mode is selected by m...

Страница 6: ...connection and commission ing 2 3 Muting sensors Throughbeam or retro reflective photoelectric sensors with activation input PNP HIGH active can be used as muting senders for the MSI 420 TMC 03 2 4 P...

Страница 7: ...sons enter the area Make sure that no persons can reach the danger zone alongside the transport material during muting Make sure that muting is only temporarily activated and only as long as the acces...

Страница 8: ...them to follow the predefined signal change within the predefined time The muting function is ready as soon as testing of Start 1 and Start 2 has been successfully completed If tR is exceeded muting...

Страница 9: ...5 ms after Start 1 has been interrupted Start 2 is also allowed to be interrupted by the trans port material During this phase the two muting sensors i e both start signals as well as the protective s...

Страница 10: ...ain If an error is de tected during direction monitoring the muting process is terminated and an error message is ac tivated see chapter 5 Diagnostics messages Important If Start 1 and Start 2 come fr...

Страница 11: ...g of an emergency stop muting errors or other similar circumstances If a valid override sequence with a LOW HIGH LOW transition min 350 ms and max 3 s longer or shorter pulses are ignored occurs at in...

Страница 12: ...y the cables and lines so that they are protected against external damages For further information see EN ISO 13849 2 Table D 4 TMC66 MSI 420 TMC 03 Designation Comment 1 T1 SLS activation 2 I1 SLS in...

Страница 13: ...a competent person If for example operating mode 3 has been 19 20 Q2 Safety output 2 Semiconductor output PNP n c I10 Selection of operating mode see table 4 2 Selection of operat ing mode n c I11 Se...

Страница 14: ...art inter lock In the operating mode with start restart interlock the MSI 420 TMC 03 expects two signal changes as the switch on signal sensor function A fault in the start button e g caused by welded...

Страница 15: ...es in the immediate surround ings e g safety guard properly mounted and secured against tampering If it is possible to be present undetected between the safety sensor and point of operation is an assi...

Страница 16: ...safety control the safety functions undergo a complete check Has the protective function been checked in accordance with the testing instructions given in this documentation In particular a Function...

Страница 17: ...on on the specific error Table 5 1 Diagnostics messages Safety on IQ2 Error IQ1 Error indication Q4 Status Measures Active Inactive Inactive Normal opera tion None Inactive Active Active 1x every 5 se...

Страница 18: ...ons who have been instructed to do so If changes have been made to the machine or protective device or the safety control has been modified or repaired then check the system again according to the che...

Страница 19: ...Leuze electronic MSI 420 TMC 03 17 8 EU EC Declaration of Conformity...

Страница 20: ...Leuze electronic MSI 420 TMC 03 18...

Отзывы: