7.3 Setting up the light curtains
NOTICE
Observe correct installation and alignment!
Make sure that the light curtains are correctly installed and aligned, see chapter 5.2.1ff.
Make sure that the light curtains are correctly connected to each other and to the LSC-Box, see
chapter 6.3.
NOTICE
Important for transparent objects!
When measuring
transparent objects
(e.g. six-pack drinks), the "Sensitivity" parameter must
be adjusted via WebConfig, see Chapter 8.2.1!
The "sensitivity" of the CMS 700i is the reciprocal of the "functional reserve" of the CML 730i
light curtains.
A technical explanation can be found in the CML 730i manual, parameter "Function reserve"
chapter 8.4, p. 70ff.
Switch on the LSC box so that the light curtains are energized.
NOTICE
Setting light curtains!
Parameterize the light curtains on the receiver control panel, the changes take effect directly
without a restart.
7.3.1 Setting up the height and width light curtain
The necessary configuration for the height and width light curtain is as follows:
Process data length (PD Length): 32 Bytes
Bit rate: COM3: 230,4
Data storage: Deactivated
The configuration in the Receiver Panel menu is as follows:
Level 0
Level 1
Level 2
Description
Main
Settings
Commands