background image

Technician Service Guide                                                                                                                               33367B

9

If the measured AC voltage indicates the
transformer has failed, indicated by significantly
lower voltage readings, replace the transformer with
the replacement service part specified on the parts
list for the model of charger being serviced.

Charger

Nameplate

DC Voltage

No Load

Output Coil

AC Voltage*

No Load

Auxiliary Coil

AC Voltage

12

28-44

24

56-90

36

90-126

48

120-168

24-32

Note: The voltage readings are approximate and
transformer failure is indicated when the
measured AC voltages are SIGNIFICANTLY
LOWER than the listed values.

(*) The wide AC voltage range is the result of
various AC line voltages that many charger
models have been designed to operate on.

Table 2

If it should become necessary to replace a terminal
on one of the transformer leads, the new terminal
must be crimped AND soldered.

SECTION 4 – SCR TESTING

The feedback  control design of the charger makes it
possible for one SCR in the SCR assembly to not
function and the charger to still have some output.
This condition can be detected by noting the
temperature of the separate SCRs and replacing the
complete assembly if one of the SCRs feels cold
and the other hot.  This condition may also suggest
it’s presence by continual melting of the DC fuse,
see 

Section 6 – Charger DC Circuit Breaker

Trips/Fuse Blows 

for additional information.

An SCR can fail in a shorted or open mode.  Shorted
SCRs can be detected by measuring the resistance
between the legs of the SCR with an ohm-meter.  An
SCR that is shorted Anode to Cathode will cause the
DC circuit breaker to trip or fuse to blow, see

Section 6 – Charger DC Circuit Breaker
Trips/Fuse Blows

 for more information.  An SCR

with a shorted anode to gate can be detected by
measuring the resistance between the anode to
gate.  To do so, first disconnect the charger AC
power plug from the outlet and the DC output cord
from the equipment charging receptacle.  Remove
the charger’s cover and carefully remove the control
cable edge connector from the electronic timer.

Locate the in-line bullet connectors on the brown
leads (gate) of the SCRs and disconnect, see figure
6.

Figure 6

Using an ohm-meter, measure the resistance
between between the brown gate lead of the SCR
and the heatsink plate (SCR anode).  Test each
SCR separately.  Connect the positive (+) lead of the
ohm-meter to the heatsink plate (anode) of one
SCR.  Connect the negative (-) lead of the ohm-
meter to the brown gate lead for that same SCR.
The resistance for a good SCR should be about 20
megohms.  Reverse the leads of the ohm-meter and
test the SCR again.  Resistance for a good SCR
should be in the megohms.

The resistance of a failed SCR, regardless of ohm-
meter polarity, will be about 50 ohms.

If an SCR with a shorted anode to gate is located,
the electronic timer has been damaged and must be
repaired or replaced with the SCR assembly.

WARNING: ALWAYS TEST SCRs  BEFORE
REPLACING AN ELECTRONIC TIMER.  DAMAGE
AND SUBSEQUENT FAILURE WILL OCCUR TO
ALL ELECTRONIC TIMERS INSTALLED IN A
CHARGER THAT CONTAINS A SHORTED
ANODE TO GATE SCR, IF CONNECTED TO AC
POWER.

DANGER:  HAZARD OF ELECTRIC SHOCK!

THE FOLLOWING TEST REQUIRES THE
CHARGER TO BE CONNECTED TO A LIVE AC
OUTLET.  FOLLOW ALL ELECTRICAL SAFETY
PRECAUTIONS TO AVOID ELECTRIC SHOCK!

Содержание 33367

Страница 1: ...OR SERVICE TO THE CHARGER TURNING THE CHARGER OFF DOES NOT REDUCE THIS RISK WARNING DO NOT OPERATE THE CHARGER IF IT IS MALFUNCTIONING PERSONAL INJURY OR PROPERTY DAMAGE COULD RESULT WARNING DO NOT TOUCH THE BATTERY TERMINALS OR CONTACTS ON THE CHARGING PLUG AN ELECTRIC SHOCK COULD RESULT This service guide applies to most portable style SCR regulated charger designs but not all This service guide...

Страница 2: ...ratures Batteries allowed to sit unmaintained in storage will self discharge sulfate to various degrees and lose capacity Repeated charging will generally result in the recovery of most of the battery s capacity though some permanent loss can be expected BATTERY TYPES Battery manufacturers frequently use the same battery cases for different battery types Replaceable liquid electrolyte deep cycle b...

Страница 3: ...equired for the charger to recognize a battery is connected varies by model Table 1 will provide general guidelines for testing but may not represent the actual minimum voltage which may be lower Charger Nameplate DC Voltage Typical DC Voltage Required 12 8 24 16 36 25 48 33 Table 1 Inspect and test for good AC and DC fuses circuit breakers before proceeding with this test If either the AC or DC f...

Страница 4: ...e wires as shown on the service wiring diagram If no DC voltage is measured or the DC voltage measured is lower than the DC voltage measured at test points E F repair or replace the control cable assembly See figure 2 Figure 2 If the DC voltage measured at the electronic timer edge connector or flag terminals is correct testing of the AC line voltage must be performed DANGER HAZARD OF ELECTRIC SHO...

Страница 5: ... not illuminate after transformer replacement the electronic timer must be repaired or replaced Replace the electronic timer with the replacement service part specified on the parts list for the specific model of charger being serviced and confirm indicator light illumination WARNING ALWAYS TEST SCRs BEFORE REPLACING AN ELECTRONIC TIMER DAMAGE AND SUBSEQUENT FAILURE WILL OCCUR TO ALL ELECTRONIC TI...

Страница 6: ... replace failed DC fuse fuseholder circuit breaker and or ammeter as needed and retest If the charger passes both the Test for battery voltage increase and Inspect and test charger DC circuit proceed to Section 3 Part A Test for correct transformer output coil voltage If the transformer output coil voltage test indicates a failed transformer retest charger for proper operation after transformer re...

Страница 7: ...cid batteries there are two ways to test if the electrochemical reaction has actually ceased 1 An accurate hydrometer can be used to determine cessation of the electrochemical charging reaction If the measured specific gravity of several cells does not increase in three 3 consecutive readings taken one hour apart while the charger continues to charge the charger is operating too long 2 An accurate...

Страница 8: ...the transformer output coil leads and compare to the values in table 2 Figure 4 If the measured AC voltage indicates the transformer has failed indicated by significantly lower voltage readings replace the transformer with the replacement service part specified on the parts list for the model charger being serviced Part B Test for correct transformer auxiliary coil voltage Disconnect the AC power ...

Страница 9: ...Anode to Cathode will cause the DC circuit breaker to trip or fuse to blow see Section 6 Charger DC Circuit Breaker Trips Fuse Blows for more information An SCR with a shorted anode to gate can be detected by measuring the resistance between the anode to gate To do so first disconnect the charger AC power plug from the outlet and the DC output cord from the equipment charging receptacle Remove the...

Страница 10: ...or chargers without an ammeter an in line ammeter may be used in the DC charging circuit to test for current flow or a DC voltmeter may be used to test for momentary battery voltage increase If the ammeter does not indicate current flow for each SCR the SCR not causing ammeter deflection has failed and the SCR assembly must be replaced SECTION 5 CHARGER AC CIRCUIT BREAKER TRIPS FUSE BLOWS Before p...

Страница 11: ...KER TRIPS FUSE BLOWS This condition can be caused by a charger problem a weak fuse or circuit breaker protecting the circuit or an overloaded circuit If the building AC power fuse or circuit breaker blows connect the charger to other outlets on different circuits in the building If the charger operates properly on other circuits have a qualified electrician check the original circuit If the charge...

Страница 12: ...lectrical com SERVICE WIRING DIAGRAM BLACK AC VOLTAGE SELECTOR SWITCH POWER SWITCH BLACK GREEN WHITE 100 125 200 250 VAC INPUT WHITE WHITE AC FUSE 1b 1a 2b 2a BROWN BROWN GRAY BLACK AC FUSE TRANSFORMER SCR BLACK BLACK BLACK SCR BLACK 1 2 3 4 9 10 11 12 SHUNT YELLOW BROWN BROWN WHITE DC OUTPUT AMMETER 40 AMP CIRCUIT BREAKER BLACK BLACK BLUE NATURAL BLUE ELECTRONIC TIMER 5 6 7 8 SHOWN IN 100 125 VOL...

Отзывы: