2
SPECIFICATIONS
SUPPLY VOLTAGE:
115 VOLTS 50/60 HZ
230 VOLTS 50/60 HZ
24V DC
OPERATING VOLTAGE RANGE:
90 TO 110% OF RATED VOLTAGE
POWER CONSUMPTION:
10 WATTS (MAX.), .7W STEADY STATE
INPUT:
4 - 20 mA (STD), PROTECTED AGAINST ACCIDENTAL 24V
INPUT TO THE CURRENT INPUT TERMINALS
RTD (OPTIONAL)
OUTPUT:
4-20 mA(STD), ACCURACY ±5% SPAN; MAX LOAD = 350
Ω
CONTROL ACTION:
DIRECT OR REVERSE (SWITCH SELECTABLE)
LOCAL SET POINT ADJUSTMENT:
PUSH BUTTON SWITCHES AND DIGITAL DISPLAY
REMOTE SET POINT ADJUSTMENT:
4 - 20mA STANDARD INPUT, DEFAULTS ON LOSS OF SIGNAL
DISPLAY MODES:
CALIBRATION (HIGH/LOW), SET POINT, PROCESS VALUE,
DEVIATION
AIR SUPPLY:
100 PSI MAX., 40 MICRON FILTERED
OUTPUT:
0 TO MAXIMUM SUPPLY PRESSURE
AIR CONSUMPTION:
NO AIR CONSUMPTION AT STEADY STATE
DISPLAY:
3-1/2 DIGIT LCD BACKLIT DISPLAY (GREEN BACKGROUND)
ACCURACY:
±0.5% OF FULL SPAN
SETTING ACCURACY:
ACTUAL SET VALUE COINCIDES WITH INDICATED SET VALUE
RESPONSE SPEED RANGE:
200:1
AMPLIFIER GAIN (SLOW LOOP):
NORMAL= 6(MAX); HIGH = 12(MAX)
DEAD BAND:
ADJUSTABLE FROM ±0% TO 5% OF FULL SPAN
INPUT RESISTANCE TO CURRENT
LOOP:
100 OHMS X CURRENT + 0.7 VOLTS
AMBIENT TEMPERATURE:
-4°F TO 140°F (-20° TO 60°C)
(HEATERS FOR -40°F OPTIONAL)
WEIGHT:
8 LBS. (3.6KG)
OVERALL DIMENSIONS
(INCLUDING MOUNTING BRACKET):
9.75” WIDE X 13.5” HIGH X 6.3” DEEP (25CM X 34CM X 17CM)
ENCLOSURE APPROVAL
NEMA 1-2-3-3S-4-4X-12-13.
ENCLOSURE MATERIALS:
ENCLOSURE: NORYL
HINGED COVER: POLYCARBONATE
PNEUMATIC FITTINGS:
1/8 NPT (FEMALE)
AIR DELIVERY:
SOLENOID FULLY OPEN:
0.76 SCFM AT 30 PSI
1.23 SCFM AT 60 PSI
1.71 SCFM AT 90 PSI
AUTO/MANUAL:
ALLOWS MANUAL OPERATION OF SOLENOID VALVES TO
LOAD OR VENT THE ACTUATOR