VARMECA
13
3.3 - Electrical and electromagnetic phenomena
The VARMECA conforms to electromagnetic compatibility directive 89/336/EEC, modified by
92/31/EEC, provided it is fitted with the EMC filter option.
3.4 - Description of cables and protections
• When using a circuit-breaker, it must be a motor circuit-breaker.
• Comply with size of protection fuses.
• Cable size may vary according to current national standards, which take
precedence over the values given in the table below without exception.
• These tables should never be used instead of current standards.
Note : The value of the mains current is a typical value which depends on the source
impedance. The higher the impedance, the lower the current.
VARMECA
Power
3-phase mains 400V
±
10 %
rating
(kW)
Current (A)
gl fuses (A)
Cables (mm
2
)
37
0,37
1,7
3
1,5
55
0,55
2,2
3
1,5
75
0,75
3
4
1,5
90
0,9
3,5
6
1,5
110
1,1
4,1
6
1,5
150
1,5
5,3
6
1,5
180
1,8
6,2
8
2,5
220
2,2
7,7
10
2,5
300
3
8,9
16
2,5
400
4
10
16
2,5