Derating curves 

and losses

Drive voltage 

levels

DC bus 

design

Mechanical 

installation

EMC filters

Line chokes

Motor cable 

lengths

General 

data

I/O 

specification

Supply 

types

Options

Digidrive SK Technical Data                                                                                                                                                                                        

19

Issue Number: a                                                          www.leroy-somer.com

Key to Table 6-3

Conformity

The requirements are listed in descending order of severity, so that if a particular requirement is met then all requirements listed after it are also met.

N

Where the drive is incorporated into a system with rated input current exceeding 100A, the higher emission limits of EN 61800-3 for the second 
environment are applicable, and no filter is then required.

N

Operation without an external filter is a practical cost-effective possibility in an industrial installation where existing levels of electrical noise are likely 
to be high, and any electronic equipment in operation has been designed for such an environment. This is in accordance with EN 61800-3 in the 
second environment, with restricted distribution. There is some risk of disturbance to other equipment, and in this case the user and supplier of the 
drive system must jointly take responsibility for correcting any problem which occurs.

Standard

Description

Frequency range

Limits

Application

R

EN 61000-6-3 

(previously EN 

50081-1)

Generic emission 

standard for the 

residential commercial 

and light - industrial 

environment

0.15 - 0.5MHz

limits decrease linearly 

with log frequency

66-56dB

µ

V quasi peak

56-46dB

µ

V average

AC supply 

lines

0.5 - 5MHz

56dB

µ

V quasi peak

46dB

µ

V average

5 - 30MHz

60dB

µ

V quasi peak

50dB

µ

V average

EN 61800-3

IEC 61800-3

Product standard for 

adjustable speed power 

drive systems

Requirements for the first environment

1

, with unrestricted 

distribution

I

EN 61000-6-4 

(previously EN 

50081-2)

Generic emission 

standard for the 

industrial environment

0.15 - 0.5MHz

79dB

µ

V quasi peak

66dB

µ

V average

AC supply 

lines

0.5 -30MHz

73dB

µ

V quasi peak

60dB

µ

V average

EN 61800-3

IEC 61800-3

Product standard for 

adjustable speed power 

drive systems

Requirements for the first environment

with restricted 

distribution

2

E2U

EN 61800-3

IEC 61800-3

Product standard for 

adjustable speed power 

drive systems

Requirements for the second environment with unrestricted 

distribution

E2R

EN 61800-3

IEC 61800-3

Product standard for 

adjustable speed power 

drive systems

Requirements for the second environment with restricted 

distribution

2

Operation in this condition is not recommended

1

The first environment is one where the low voltage supply network also supplies domestic premises

2

When distribution is restricted, drives are available only to installers with EMC competence

This caution applies where the drive is used in the first environment according to EN 61800-3.
This is a product of the restricted distribution class according to IEC 61800-3. In a domestic environment this 
product may cause radio interference in which case the user may be required to take adequate measures.

CAUTION

NOTE

NOTE

Содержание DIGIDRIVE SK Series

Страница 1: ......

Страница 2: ...acts of its manufacturing operations and of its products throughout their life cycle To this end we operate an Environmental Management System EMS which is certified to the International Standard ISO...

Страница 3: ...perature 23 9 4 Storage temperature 23 9 5 Altitude 23 9 6 Humidity 23 9 7 Storage humidity 23 9 8 Pollution degree 23 9 9 Materials 23 9 10 Vibration 23 9 11 Frequency accuracy 24 9 12 Resolution 24...

Страница 4: ...7 2 2 3 0 4 0 5 2 7 0 9 6 150 overload current for 60s A 2 6 3 3 4 5 6 7 8 10 5 14 4 Typical full load input current A 4 3 5 8 8 1 10 5 14 2 6 7 17 4 8 7 23 2 11 9 Maximum continuous input current A 9...

Страница 5: ...put current A 1 3 1 7 2 1 2 8 3 8 5 1 7 2 9 0 150 overload current for 60s A 2 2 6 3 2 4 2 5 7 7 7 10 8 13 5 Typical full load input current A 1 7 2 5 3 1 4 5 2 7 3 9 5 11 9 Maximum continuous input c...

Страница 6: ...tor temperatures At 12 and 18kHz the limiting factor tends to be the heatsink temperature At 3 and 6kHz operating outside the de rating curves will cause some of the capacitors within the drive to run...

Страница 7: ...ply types Options Digidrive SK Technical Data 7 Issue Number a www leroy somer com Figure 2 2 Digidrive SK Size A 0 37kW derating curve Figure 2 3 Digidrive SK Size A 0 55kW derating curve 0 0 5 1 0 2...

Страница 8: ...es at the de rating curve points Table 2 1 Digidrive SK size A 0 25kW losses Table 2 2 Digidrive SK size A 0 37kW losses Table 2 3 Digidrive SK size A 0 55kW losses Ambient Temperature C Loss W 3kHz 6...

Страница 9: ...filters Line chokes Motor cable lengths General data I O specification Supply types Options Digidrive SK Technical Data 9 Issue Number a www leroy somer com Table 2 4 Digidrive SK size A 0 75kW losses...

Страница 10: ...o the next floor There is no de rating as such when low DC bus operation is enabled however the power will be limited by the reduced voltage and ripple generated on the DC bus of the drive Figure 3 1...

Страница 11: ...2 negative phase sequence IEC 146 1 1 Immunity class C 3 1 3 Three phase 400V 380V to 480V 10 48Hz to 62Hz Phase imbalance 3 between phases or 2 negative phase sequence IEC 146 1 1 Immunity class C It...

Страница 12: ...110 940 44 2 5M TL SKBD200150 1410 44 3 5M TL SKCD200220 1880 66 LS Model CT Model DC Bus Capacitance F DC bus inductance mH Inrush resistance at 25oC 1T SKB3400037 165 44 1 2T SKB3400055 165 44 1 5T...

Страница 13: ...ize A mounting dimensions N If DIN rail mounting is used in an installation where the drive is to be subjected to shock or vibration it is recommended that the bottom mounting screws are used to secur...

Страница 14: ...rail mounting is used in an installation where the drive is to be subjected to shock or vibration it is recommended that the bottom mounting screws are used to secure the drive to the back plate If t...

Страница 15: ...lengths General data I O specification Supply types Options Digidrive SK Technical Data 15 Issue Number a www leroy somer com Figure 5 3 Size C mounting dimensions Size C is not DIN rail mountable A B...

Страница 16: ...Line chokes Motor cable lengths General data I O specification Supply types Options 16 Digidrive SK Technical Data www leroy somer com Issue Number a 5 2 Minimum mounting clearances Figure 5 4 Minimum...

Страница 17: ...4 14 07 LL Y Y Y 3 5T to 5 5T SKC3400220to SKC3400400 3 FS6514 14 07 Y Y Y FS6514 14 07 LL Y Y Y Used with Number of phases Schaffner reference Power losses at rated current IP rating Weight Operation...

Страница 18: ...z 3kHz 6kHz 12kHz 18kHz 3kHz 6kHz 12kHz 18kHz 0 5M and 1M SKA1200025 and SKA1200037 1 5 E2U E2U E2R E2R R I I I R I I I 10 E2U E2R E2R E2R R I I I R I I I 20 E2R R I I I I 30 E2R I I 50 E2R I 1 2M and...

Страница 19: ...15 0 5MHz limits decrease linearly with log frequency 66 56dB V quasi peak 56 46dB V average AC supply lines 0 5 5MHz 56dB V quasi peak 46dB V average 5 30MHz 60dB V quasi peak 50dB V average EN 61800...

Страница 20: ...5in M4 8 7mm 0 34in 4 5mm 0 17in FS6513 10 07 209mm 8 22in 237 7mm 9 35in 50mm 1 96in 40mm 1 57in 20mm 0 78in 193 5mm 7 61in 257 2mm 10 12in 14 AWG M4 80mm 3 15in M4 8 7mm 0 34in 4 5mm 0 17in FS6513 1...

Страница 21: ...ffect the drive Table 7 1 Characteristics Dimensions and weight These are given by way of example and may vary depending on the manufacturer Table 7 2 Dimensions and weight Digidrive SK ratings Seff r...

Страница 22: ...ble means that the cable length limits shown in table 8 1 must be observed Failure to do so can result in spurious OI AC tripping of the drive If longer cable lengths are required consult LEROY SOMER...

Страница 23: ...temperature of 10 C 14 F 9 4 Storage temperature 40 to 60 C 40 to 140 F for 12 months max 9 5 Altitude Rated altitude 1000m 3250 ft Reduce the normal full load current by 1 for every 100m 325 ft abov...

Страница 24: ...must charge the dc bus and SMPS outputs and stabilise to allow the control processor to start operation in the following times 9 16 Serial communications Modbus RTU 9 17 Switching frequencies The soft...

Страница 25: ...Volt Scaling Input range automatically scaled to Pr 01 Minimum set speed to Pr 02 Maximum set speed Input impedance 200 current 100k voltage Resolution 0 1 Accuracy 2 Sample time 6ms Absolute maximum...

Страница 26: ...triggered apart from after a trip where they become edge triggered See and above If the enable and run forward or enable and run reverse terminals are closed when the drive is powered up the drive wi...

Страница 27: ...he beginning of each menu there is a single line parameter description and this contains the update rate for each parameter This time signifies the task routine time in the software that the parameter...

Страница 28: ...or To ensure that the motor and cable are protected against overload the drive must be programmed with the correct motor rated voltage Electric shock risk The voltages present in the following locatio...

Страница 29: ...ype A can only be used with single phase drives Type B must be used with three phase drives It is recommended that only Type B RCDs be used with inverter drives If an external EMC filter is used a del...

Страница 30: ...11 7 Use of earth leakage circuit breakers ELCB residual current device RCD There are three common types of ELCB RCD Type AC detects AC fault currents Type A detects AC and pulsating DC fault currents...

Страница 31: ...tion with Digidrive SK 03 00 00 Yes Beige SM Ethernet Ethernet option Ethernet adapter for communication with Digidrive SK 03 00 00 Yes Extended IO Dark Yellow SM I O Lite I O Lite option Increases th...

Страница 32: ...ve equipment No AC input line reactors To reduce supply harmonics Cable management SK Bracket Cable management bracket UL type 1 kit Bottom metal gland plate top cover and side covers to allow the dri...

Страница 33: ......

Страница 34: ......

Отзывы: