Derating curves 

and losses

Drive voltage 

levels

DC bus 

design

Mechanical 

installation

EMC filters

Line chokes

Motor cable 

lengths

General 

data

I/O 

specification

Supply 

types

Options

28

 Digidrive SK Technical Data

www.leroy-somer.com                                                       Issue Number: a

11      Supply types

Digidrive SK is suitable for use with any supply type, i.e. TN-S, TN-C-S, TT, IT, with a grounding at any potential, i.e. neutral, centre or corner 
('grounded-delta').
Drives are suitable for use on supplies of installation category III and lower, according to IEC60664-1.  This means they may be connected 
permanently to the supply at its origin in a building, but for outdoor installation, additional over-voltage suppression (transient voltage surge 
suppression) must be provided to reduce category IV to category III.

11.1   AC supply requirements

 Single phase drives

Single phase - Between one phase and neutral of a star connected three phase supply.

- Between two phases of a three phase supply.

Three phase models

Three-phase star or delta supply of the correct voltage.

Dual rated models

Any of the above supplies can be used.

11.2   Safety 

11.3   Cables

Recommended cable sizes are given in tables 1-2 & 1-7.  They are only a guide; refer to local wiring regulations for correct size of cables. In some 
cases, a larger cable size is required to avoid excessive voltage drop.
Use 105

°

C (221

°

F) (UL 60/75

°

C temp rise) PVC-insulated cable with copper conductors having a suitable voltage rating, for the following power 

connectors:

AC supply to external EMC filter (when used)

AC supply (or external EMC filter) to drive

Drive to motor

Drive to braking resistor

Motor cables

The recommended output cable sizes assume that the motor maximum current matches that of the drive.  Where a motor of reduced rating is used, 
the cable rating may be chosen to match that of the motor.  To ensure that the motor and cable are protected against overload, the drive must be 
programmed with the correct motor rated voltage.

Electric shock risk 

The voltages present in the following locations can cause severe electric shock and may be lethal:

AC supply cables and connections

DC and brake cables and connections

Output cables and connections

Many internal parts of the drive, and external option units

Unless otherwise indicated, control terminals are single insulated and must not be touched.

Isolation device

The AC supply must be disconnected from the drive using an approved isolation device before any cover is removed from the drive or 
before any servicing work is performed.

STOP function

The STOP function does not remove dangerous voltages from the drive, the motor or
any external option units.

Stored charge

The drive contains capacitors that remain charged to a potentially lethal voltage after the AC supply has been disconnected. If the drive 
has been energized, the AC supply must be isolated at least ten minutes before work may continue.
Normally, the capacitors are discharged by an internal resistor. Under certain, unusual fault conditions, it is possible that the capacitors 
may fail to discharge, or be prevented from being discharged by a voltage applied to the output terminals. If the drive has failed in a 
manner that causes the display to go blank immediately, it is possible the capacitors will not be discharged. In this case, consult LEROY-
SOMER.

Equipment supplied by plug and socket

Special attention must be given if the drive is installed in equipment which is connected to the AC supply by a plug and socket. The AC 
supply terminals of the drive are connected to the internal capacitors through rectifier diodes which are not intended to give safety 
isolation. If the plug terminals can be touched when the plug is disconnected from the socket, a means of automatically isolating the plug 
from the drive must be used (e.g. a latching relay).

WARNING

WARNING

WARNING

WARNING

WARNING

Содержание DIGIDRIVE SK Series

Страница 1: ......

Страница 2: ...acts of its manufacturing operations and of its products throughout their life cycle To this end we operate an Environmental Management System EMS which is certified to the International Standard ISO...

Страница 3: ...perature 23 9 4 Storage temperature 23 9 5 Altitude 23 9 6 Humidity 23 9 7 Storage humidity 23 9 8 Pollution degree 23 9 9 Materials 23 9 10 Vibration 23 9 11 Frequency accuracy 24 9 12 Resolution 24...

Страница 4: ...7 2 2 3 0 4 0 5 2 7 0 9 6 150 overload current for 60s A 2 6 3 3 4 5 6 7 8 10 5 14 4 Typical full load input current A 4 3 5 8 8 1 10 5 14 2 6 7 17 4 8 7 23 2 11 9 Maximum continuous input current A 9...

Страница 5: ...put current A 1 3 1 7 2 1 2 8 3 8 5 1 7 2 9 0 150 overload current for 60s A 2 2 6 3 2 4 2 5 7 7 7 10 8 13 5 Typical full load input current A 1 7 2 5 3 1 4 5 2 7 3 9 5 11 9 Maximum continuous input c...

Страница 6: ...tor temperatures At 12 and 18kHz the limiting factor tends to be the heatsink temperature At 3 and 6kHz operating outside the de rating curves will cause some of the capacitors within the drive to run...

Страница 7: ...ply types Options Digidrive SK Technical Data 7 Issue Number a www leroy somer com Figure 2 2 Digidrive SK Size A 0 37kW derating curve Figure 2 3 Digidrive SK Size A 0 55kW derating curve 0 0 5 1 0 2...

Страница 8: ...es at the de rating curve points Table 2 1 Digidrive SK size A 0 25kW losses Table 2 2 Digidrive SK size A 0 37kW losses Table 2 3 Digidrive SK size A 0 55kW losses Ambient Temperature C Loss W 3kHz 6...

Страница 9: ...filters Line chokes Motor cable lengths General data I O specification Supply types Options Digidrive SK Technical Data 9 Issue Number a www leroy somer com Table 2 4 Digidrive SK size A 0 75kW losses...

Страница 10: ...o the next floor There is no de rating as such when low DC bus operation is enabled however the power will be limited by the reduced voltage and ripple generated on the DC bus of the drive Figure 3 1...

Страница 11: ...2 negative phase sequence IEC 146 1 1 Immunity class C 3 1 3 Three phase 400V 380V to 480V 10 48Hz to 62Hz Phase imbalance 3 between phases or 2 negative phase sequence IEC 146 1 1 Immunity class C It...

Страница 12: ...110 940 44 2 5M TL SKBD200150 1410 44 3 5M TL SKCD200220 1880 66 LS Model CT Model DC Bus Capacitance F DC bus inductance mH Inrush resistance at 25oC 1T SKB3400037 165 44 1 2T SKB3400055 165 44 1 5T...

Страница 13: ...ize A mounting dimensions N If DIN rail mounting is used in an installation where the drive is to be subjected to shock or vibration it is recommended that the bottom mounting screws are used to secur...

Страница 14: ...rail mounting is used in an installation where the drive is to be subjected to shock or vibration it is recommended that the bottom mounting screws are used to secure the drive to the back plate If t...

Страница 15: ...lengths General data I O specification Supply types Options Digidrive SK Technical Data 15 Issue Number a www leroy somer com Figure 5 3 Size C mounting dimensions Size C is not DIN rail mountable A B...

Страница 16: ...Line chokes Motor cable lengths General data I O specification Supply types Options 16 Digidrive SK Technical Data www leroy somer com Issue Number a 5 2 Minimum mounting clearances Figure 5 4 Minimum...

Страница 17: ...4 14 07 LL Y Y Y 3 5T to 5 5T SKC3400220to SKC3400400 3 FS6514 14 07 Y Y Y FS6514 14 07 LL Y Y Y Used with Number of phases Schaffner reference Power losses at rated current IP rating Weight Operation...

Страница 18: ...z 3kHz 6kHz 12kHz 18kHz 3kHz 6kHz 12kHz 18kHz 0 5M and 1M SKA1200025 and SKA1200037 1 5 E2U E2U E2R E2R R I I I R I I I 10 E2U E2R E2R E2R R I I I R I I I 20 E2R R I I I I 30 E2R I I 50 E2R I 1 2M and...

Страница 19: ...15 0 5MHz limits decrease linearly with log frequency 66 56dB V quasi peak 56 46dB V average AC supply lines 0 5 5MHz 56dB V quasi peak 46dB V average 5 30MHz 60dB V quasi peak 50dB V average EN 61800...

Страница 20: ...5in M4 8 7mm 0 34in 4 5mm 0 17in FS6513 10 07 209mm 8 22in 237 7mm 9 35in 50mm 1 96in 40mm 1 57in 20mm 0 78in 193 5mm 7 61in 257 2mm 10 12in 14 AWG M4 80mm 3 15in M4 8 7mm 0 34in 4 5mm 0 17in FS6513 1...

Страница 21: ...ffect the drive Table 7 1 Characteristics Dimensions and weight These are given by way of example and may vary depending on the manufacturer Table 7 2 Dimensions and weight Digidrive SK ratings Seff r...

Страница 22: ...ble means that the cable length limits shown in table 8 1 must be observed Failure to do so can result in spurious OI AC tripping of the drive If longer cable lengths are required consult LEROY SOMER...

Страница 23: ...temperature of 10 C 14 F 9 4 Storage temperature 40 to 60 C 40 to 140 F for 12 months max 9 5 Altitude Rated altitude 1000m 3250 ft Reduce the normal full load current by 1 for every 100m 325 ft abov...

Страница 24: ...must charge the dc bus and SMPS outputs and stabilise to allow the control processor to start operation in the following times 9 16 Serial communications Modbus RTU 9 17 Switching frequencies The soft...

Страница 25: ...Volt Scaling Input range automatically scaled to Pr 01 Minimum set speed to Pr 02 Maximum set speed Input impedance 200 current 100k voltage Resolution 0 1 Accuracy 2 Sample time 6ms Absolute maximum...

Страница 26: ...triggered apart from after a trip where they become edge triggered See and above If the enable and run forward or enable and run reverse terminals are closed when the drive is powered up the drive wi...

Страница 27: ...he beginning of each menu there is a single line parameter description and this contains the update rate for each parameter This time signifies the task routine time in the software that the parameter...

Страница 28: ...or To ensure that the motor and cable are protected against overload the drive must be programmed with the correct motor rated voltage Electric shock risk The voltages present in the following locatio...

Страница 29: ...ype A can only be used with single phase drives Type B must be used with three phase drives It is recommended that only Type B RCDs be used with inverter drives If an external EMC filter is used a del...

Страница 30: ...11 7 Use of earth leakage circuit breakers ELCB residual current device RCD There are three common types of ELCB RCD Type AC detects AC fault currents Type A detects AC and pulsating DC fault currents...

Страница 31: ...tion with Digidrive SK 03 00 00 Yes Beige SM Ethernet Ethernet option Ethernet adapter for communication with Digidrive SK 03 00 00 Yes Extended IO Dark Yellow SM I O Lite I O Lite option Increases th...

Страница 32: ...ve equipment No AC input line reactors To reduce supply harmonics Cable management SK Bracket Cable management bracket UL type 1 kit Bottom metal gland plate top cover and side covers to allow the dri...

Страница 33: ......

Страница 34: ......

Отзывы: