Ethernet Ports
M12 Interface (Auto MDI/MDIX)
⚫
Connection Format: M12 8-Pin X-Coded Female Connector
⚫
Transmission rate: 10/100/1000 Mbit/s
Prepare the M12 8-Pin X-Coded Ethernet Port mating cable for Ethernet connection. The M12 X-Coded
Ethernet ports are auto-sensing for 10Base-T, 100Base-TX, or 1000Base-T devices connections. Auto
MDI/MDIX means that you can connect to another switch or workstation without changing straight through
or crossover cabling. See pin assignment shown in Table 2.2
M12 8-Pin X-Coded Female Connector
Pinouts
10/100Base-T(X) Signal
1000Base-T Signal
1
Transmit Data + (TX+)
BI_DA+
2
Transmit Data - (TX-)
BI_DA-
3
Receive Data + (RX+)
BI_DB+
4
Receive Data - (RX-)
BI_DB-
5
BI_DD+
6
BI_DD-
7
BI_DC-
8
BI_DC+
Table 2.2
Note:
“+” and “
-
” signs represent the polarity of the wires that make up each wire pair.
Connection of Cables
Use the twisted-pair cable, category 5e or the above cabling for M12 port connections. The cable between
the Ethernet switch and the link partner (switch, hub, workstation, etc.) must be less than 100 meters (328
ft.) long.
⚫
Minimum Wire Gauge: 24AWG
⚫
Maximum Transmission Length: 100m (328ft)
Caution:
Please use with copper conductors only
Attention:
DESTINÉ À ÊTRE UTILISÉ AVEC DES CONDUCTEURS EN CUIVRE SEULEMENT
Caution:
Use conductors with insulation rated for at least 60°C
Attention:
AVERTISSEMENT: EMPLOYER DES CONDUCTEURS POUR AU MOINS 60°C
Caution:
Base the conductor Ampacity on a maximum termination temperature of 60°C
Attention:
LE COURANT ADMISSIBLE DU CONDUCTEUR DOIT ÊTRE DÉTERMINÉ EN FONCTION D’UNE TEMPÉRATURE
MAXIMALE AUX TERMINAISONS DE 60°C