27
CMVETH01B
Cyclic Data Access
When this is done Status Output must be mapped to Assembly 109. This value is required
STOP!
The Status Input Assembly is limited to supporting two 16-bit words. The user can
either use assembly 70, 71 or 106 for this purpose. If using Assembly 106 as the
status input, the user
must
set the length to 2 and
must
set P452 and P453 to 0.
5.2 Implicit Messaging Timeout
It is often desirable to set a fault timeout condition to prevent the drive from operating in a runaway
condition or loss of communications. To do this while controlling the drive via implicit messaging, set P431,
P432 and P434 to 0. Set the timeout period desired (in milliseconds) in P435.
5.3 Saving the Configuration
After adding the scanner (or bridge) and the adapter to the I/O configuration, the configuration must be
downloaded to the controller. The configuration should also be saved to a file on your computer.
1. On the top toolbar, click [Communications] then select [Download] from the pull down menu. The
Download dialog box will open.
NOTE
If a message box reports that RSLogix is unable to go online, then select ‘Communications Who
Active’ to try and find your controller in the ‘Who Active’ dialog box. If the controller is not shown,
then the Ethernet/IP driver needs to be added or configured in RSLinx. Refer to the RSLinx online help.