Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018
29
Commissioning
Settings in the »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4
Settings in the »Engineer«
Select the
project element
POWERLINK in the
project tree
.
• The workspace now displays the codes you can use to make the POWERLINK settings.
Parameters
Lenze setting
Info
0x1E40.2 IP Address
0xC0A86401
Read only
• The IP address is derived from the node address
(node ID):
192.168.100.[Node ID]
.
• The Lenze setting corresponds to the IP address
192.168.100.1 (0xC0.A8.64.01).
0x1E40.3 Subnet Mask
Read only
0x1E40.5 IP Address Router
3232261374
Lenze setting (hex): 0xC0A864FE =
192.168.100.254
0x1030.5 MAC Address
Read only
SoC Cycle Counter
Read only
0x1F8C NMT Communica-
tion Status
Read only
0x1F93.1 Node ID
Read only
0x1F93.2 Node ID by HW
Read only
Emergency data load
Read only
Bus error
Read only
0x1F9A Host Name
DNS-compatible device name. The length is limit-
ed to 20 characters. The device name must be non-
ambiguous within the network domain.
Node ID SW
0
Setting of the node ID, unless a node ID is set via
DIP switches.
Current address switch
Read only