Electrical installation
Three−phase AC motor operation on a frequency inverter
29
Lenze ¯ BA 33.0008 ¯ 5.0
6.2
Three−phase AC motor operation on a frequency inverter
m500−P, m540−P, and m550−P three−phase AC motors are optimised and qualified for
the use on Lenze frequency inverters and
can
be combined without any restrictions.
When actuating the motors on a third−party inverter, the voltage peaks (V
pk
) at a
given rise time (t
R
) that are shown in the diagram must not be exceeded.
0.2
0.4
0.6
0.8
1.0
1.2
0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
1.56 kV
tr ( s)
m
U
pk
(kV
)
0.1
0.3
0.5
0.7
0.9
1.1
MT−m500−001.des
Fig. 1
Permissible voltage peaks for actuation on the frequency inverter
IEC/TS 60034−25:2007 (corresponds to IVIC C/B/B @500 V): m540−P
Lenze standard A+: m500−P, m550−P
Possible counteractive measures
If it cannot be excluded that the permissible voltage peaks are exceeded, suitable
counteractive measures have to be implemented:
¯
Reduction of the DC−bus voltage (threshold for brake chopper voltage);
¯
Use of filters, chokes;
¯
Use of special motor cables.
6.3
EMC−compliant wiring
The EMC−compliant wiring of the motors is described in detail in the operating
instructions for the Lenze inverters.
¯
Using metal EMC cable glands with shield connection.
¯
Shield connection at the motor and the device.
¯
Shield connection at the terminal strip encoder.