Troubleshooting and fault elimination

Maloperation of the drive

12

l

EDK82EVXXX EN 2.0

3

Troubleshooting and fault elimination

3.1

Maloperation of the drive

Fault

Cause

Remedy

Motor does not rotate

DC-bus voltage too low
(Red LED is blinking every 0.4 s;
keypad display

LU

)

Check mains voltage

Controller inhibited
(Green LED is blinking, keypad display:

,

)

Remove the controller inhibit, controller inhibit can be set
through several sources

Automatic start inhibited (C0142 = 0 or 2)

LOW-HIGH signal at X3/28
If necessary, correct start condition (C0142)

DC injection brake active (DCB)

Deactivate DC injection brake

Mechanical motor brake is not released

Manual or electrical release of mechanical motor brake

Quick stop (QSP) active (keypad display:

,

)

Remove quick stop

Setpoint = 0

Setpoint selection

JOG setpoint activated and JOG frequency = 0

JOG setpoint selection (C0037 ... C0039)

Active fault

Eliminate fault

Wrong parameter set active

Change to correct parameter set via terminal

Control mode C0014 = -4-, -5-, but no motor parameter identification

Motor parameter identification (C0148)

Under C0410 several functions which exclude each other, are assigned
to the same signal source.

Correct configuration in C0410

Use internal voltage source X3/20 for function modules Standard I/O,
INTERBUS, PROFIBUS-DP or LECOM-B (RS485):
Bridge between X3/7 and X3/39 is missing

Bridge terminals

Motor does not rotate

Defective motor cable

Check motor cable

Motor does not rotate

smoothly

Maximum current set too low (C0022, C0023)

Adaptation to the application

y

Motor underexcited or overexcited

Check parameter setting (C0015, C0016, C0014)

C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not
adapted to the motor data

Manual adaptation or identification of motor parameters
(C0148)

Current consumption of

Setting of C0016 too high

Correct setting

Current consumption of

motor too high

Setting of C0015 too low

Correct setting

g

C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not
adapted to the motor data

Manual adaptation or identification of motor parameters
(C0148)

Motor rotates, setpoints are

“0”

With the function

3

of the keypad a setpoint has been selected.

Set the setpoint to ”0” by C0140 = 0

Motor parameter

identification stops with

Motor too small compared with rated power

identification stops with

error LP1

DC brake active via terminal

Unacceptable drive response

with vector control

various

Vector control optimisation

Torque dip in the field

weakening range

various

Contact Lenze

Stalling of the motor when

operating in the field

weakening range

Содержание Global Drive 8200 vector

Страница 1: ...L Information for the operator of the machine system EDK82EVXXX P2F Global Drive 8200 vector frequency inverter 0 25 90 kW P2F...

Страница 2: ...kW Inverter Input Output 8200 vector Type _ K For detailed information refer to the manual EDK82EV222 Id No Made in Germany 1D74 Industrial Control Equipment D 31855 Aerzen Hans Lenze Str 1 Prod No Se...

Страница 3: ...Drive controllers are components which are designed for installation in electrical systems or machinery They are not to be used as household appliances They are intended exclusively for professional a...

Страница 4: ...ry adapt the controllers to your application Please observe the corresponding information given in the Instructions After the controller has been disconnected from the supply voltage live components a...

Страница 5: ...be used as safety brakes It cannot be guaranteed that factors which cannot be influenced such as oil ingression because of a defective A side shaft seal do not cause a torque reduction Transport stora...

Страница 6: ...and the box itself must be sealed against dust and water For the trial run without output elements lock the key Check brakeoperation before commissioning of low voltage machines with brakes Operation...

Страница 7: ...heatsink of the controller has an operating temperature of 80 C Direct skin contact with the heatsink results in burnings Controller protection z All pluggable connection terminals must only be conne...

Страница 8: ...graph Signal word Possible consequences if the safety information are Signal word Meaning safety information are disregarded Danger Impending danger for persons Death or most severe injuries Dangerous...

Страница 9: ...f k i h PS m n op q r Hi Hz sh rpm C m A V Lo z y w x v t u s 88800 0050000 1 a b c d e j g f k i h PS m n op q r Hi Hz sh rpm C m A V Lo 88888 8888888 8 a b c d e j g f k i h PS m n op q r Hi Hz sh r...

Страница 10: ...bcode number 2 Change the parameter value of a sub code Five digit display of the current value 1 Display of values longer than 5 digits 1 H high order positions Display HI L low order positions Displ...

Страница 11: ...igital signals must be used to activate a parameter set for operation configuration with C0410 z In the function 0 the display shows the parameter set which is just active during operation Step Keys R...

Страница 12: ...quency Display Output frequency without slip compensation C0034 Setpoint selection range 0 Standard I O X3 8 0 5 V 0 10 V 0 20 mA C0034 Setpoint selection range 0 Application I O X3 1U 0 5 V 0 10 V X3...

Страница 13: ...Lo 1 j g f k i h PS 001 0 000 000 a b c d e m n op q r Hi Hz Lo 1 j g f k i h PS 0007 000 000 a b c d e m n op q r Hi Hz Lo 1 j g f k i h PS 0034 z y w x v t u s 000 000 a b c d e m n op q r Hi Hz Lo...

Страница 14: ...ect configuration in C0410 Use internal voltage source X3 20 for function modules Standard I O INTERBUS PROFIBUS DP or LECOM B RS485 Bridge between X3 7 and X3 39 is missing Bridge terminals Motor doe...

Страница 15: ...r active check under C0161 OFF 20 28 X3 880Hr 01 61 000 1 a b c d e j g f k i h PS m n op q r Hi Hz sh rpm C m A V Lo 3 1 4 5 2 6 ON z y w x v t u s 88888 8888888 8 a b c d e j g f k i h PS m n op q r...

Страница 16: ...us configuration For operation with application I O Faulty parameter setting of parameter set changeover In all parameter sets the signal parameter set changeover C0410 13 C0410 14 must be combined wi...

Страница 17: ...re 80 C Impermissibly high currents or too frequent and too long acceleration Check drive selection Check load if necessary replace defective bearings OH3 53 PTC monitoring TRIP is displayed if C0119...

Страница 18: ...to TRIP reset More than 8 fault messages in 10 minutes Depends on the error message sd5 85 Wire breakage analog input 1 Current at analog input 4 mA at setpoint range 4 20 mA Close circuit at analog i...

Отзывы: