5
Installation
5.2
Electrical installation
30
Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Pin assignment of the RJ45 sockets
Tip!
The EtherNet/IP interfaces feature an auto-MDIX function. This function adjusts the
polarity of the RJ45 interfaces so that a connection can be established irrespective of the
polarity of the opposite EtherNet/IP interface and irrespective of the type of cable used
(standard patch cable or crossover cable).
RJ45 socket
Pin
Signal
E94AYCXX004C
1
Tx +
2
Tx -
3
Rx +
4
-
5
-
6
Rx -
7
-
8
-
Note!
Dependent on the configuration of the Ethernet port of the device to be connected, we
recommend the use of a cross-over cable.