Electrical installation
Wire system bus (CAN)
4
48
EDBPM-H312 DE/EN/FR 2.0
4.2
Wire system bus (CAN)
Note!
ƒ
Only connect terminals of the same signal type.
ƒ
For further information with regard to the system bus (CAN) please
refer to the CAN Communication Manual.
Shield
CAN-
-V
CAN+ N.C.
CG LO HI
CG LO
CG LO HI
CG LO HI
HI
120
120
A
n
A
2
(H312)
A
1
h312_009
Fig.4-2
Wiring of system bus (CAN)
A
1
Bus node 1
A
2
Bus node 2
A
n
Bus node n
Please observe our recommendations for signal cables:
Specification for the transmission cable
Total length
≤
300 m
≤
1000 m
Cable type
LIYCY 2 x 2 x 0.5 mm
2
(twisted in pairs with shield)
CYPIMF 2 x 2 x 0.5 mm
2
(twisted in pairs with shield)
Cable resistance
≤
80
Ω
/km
≤
80
Ω
/km
Capacitance per unit
length
≤
130 nF/km
≤
60 nF/km