Electrical installation
Safety engineering
l
71
EDKLCFH3024−EER DE/EN 2.0
}
Danger!
Danger to life through improper installation
Improper installation of the safety engineering systems can cause an
uncontrolled restart of the drives.
Possible consequences:
ƒ
Death or severe injuries
Protective measures:
Total cable length between X60 and the connected components (e.g. sensors,
devices, etc.) > 3 m:
ƒ
It is essential to shield the cable installed between X60 and the connected
components:
– Connect the shield at least to X60 in the connector shell.
– If possible, connect the shield to the connected component as well.
Total cable length between X60 and the connected components (e.g. sensors,
devices, etc.) < 3 m:
ƒ
Unshielded wiring is permitted.
)
Note!
Please observe during transport, storage and operation:
ƒ
Cover unused connectors for control connections and interfaces with the
plastic covers provided to preserve the certified safety technology features.