Overview
Standard device
Pos.
Description
X11
24 V supply
X12
4 digital outputs
1 digital input
Nameplate, retractable
Setting of mains voltage/brake chopper threshold
Upper cap
The LED display enables fast indication of several operating states.
LED
Labelling
Colour
Description
-
-
-
OVERHEAT
Red
Overtemperature
MAINS
Green
Mains voltage OK
BRCHOP FAIL
Red
Short circuit on brake chopper
24 V
Green
24 V supply voltage OK
SSP94LED21
BRCHOP ON
Yellow
Brake chopper active
Pos.
Symbol
Description
Long discharge time
: All power terminals carry hazardous voltages for at
least 3 minutes after mains disconnection!
High discharge current
: Fixed installation and PE connection to EN 61800-5-1
required!
Electrostatic sensitive devices
: Before working on the device, personnel must
ensure that they are free of electrostatic charge!
Installation backplane
Pos.
Description
X111
Mains (supply from the top, e.g. through top-mounted filter)
DC-bus voltage (compatible to 9300 series)
X112
Mains (supply from the bottom, e.g. through side-mounted filter)
External brake resistor
X109
DC
Direct connection of axis
modules
X110
DC busbar -
EMC shield clamp
© 2006 Lenze Drive Systems GmbH, Hans-Lenze-Straße 1, D-31855 Aerzen
No part of this documentation may be reproduced or made accessible to third parties without written consent by Lenze Drive
Systems GmbH.
All information given in this documentation has been selected carefully and complies with the hardware and software described.
Nevertheless, deviations cannot be ruled out. We do not take any responsibility or liability for damages which might possibly occur.
Necessary corrections will be included in subsequent editions.
Содержание E94APNE0 4 Series
Страница 3: ...SSP94PN012...
Страница 55: ...Final works 8 55 EDK94PNE36 DE EN FR ES IT 2 0...