Error messages
Possible causes and remedies
84
Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PROFINET: IP address error [0x01bc6533]
PROFINET: Stack init error [0x01bc6534]
PROFINET: Internal error [0x01bc6650]
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
An invalid IP address has been assigned by the I/O cont-
roller via PROFINET or has been set in code
• Make sure that the I/O controller has assigned a valid
IP address via PROFINET.
• Set a valid IP address.
Setting the IP configuration (
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
The stack cannot be initialised with the parameters se-
lected by the user. This may be due to a station name
which does not comply with the PROFINET specification.
Check and, if necessary, adapt PROFINET parameters:
Setting the IP configuration (
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Internal error
Send communication module together with a descripti-
on of the fault to Lenze.