background image

 

RG-SFMOD

Introduction

Introduction

This  document  defines  the  specifics  required  for  Modbus  serial  communication  with  a  Lenze-AC  Tech 
standard  SCF  Series  drives  for  control,  status  monitoring,  and  programming  parameters.  A  familiarity 
with normal drive capabilities and operations is assumed. If this is not the case, refer to the SCF Series 
Installation and Operation manual (SF01) for more information.

2.1  Modbus Details

A.  AC  Tech  Drives  running  the  Modbus  communication  protocol  use  the  RTU  (Remote  Terminal  Unit) 

transmission mode and are slaves only. Therefore, the device communicating with the drives must be 
a Modbus Master. The baud rate is 9600, no parity (two stop bits). There are provisions for Odd parity 
1 stop bit and Even parity 1 stop bit as well. The bit sequence is:

DATA

Start bit

1

2

3

4

5

6

7

8

Stop bit

Stop bit

B.  At this time the AC Tech drives do not support the broadcast function of the protocol.

C.  IMPORTANT  NOTE:  Modbus  3X  and  4X  Registers  are  numbered  starting  at  1.  However,  when 

transmitted to a slave over the serial link, the actual address transmitted is one less. This is because 
the addresses are numbered starting from 0. AC Tech register numbers are also numbered starting 
from 0. Therefore, AC Tech register numbers always correspond exactly with the address transmitted. 
As  a  result,  MODBUS  REGISTER  NUMBERS  ARE  ALWAYS  ONE  GREATER  THAN  AC  TECH  REGISTER 
NUMBERS. WHENEVER THE WORDS “REGISTER #xx” APPEAR, IT SHOULD BE ASSUMED THAT THEY 
MEAN “AC TECH REGISTER xx” and the Modbus Register number will be one larger. In some instances 
we may show both for clarity. For example: “Register #24 (Modbus Register #25) . . .”

D.  The function codes supported by AC Tech drives are:

03  Read Holding Registers (4X references). In general we can read only one register at a time. However, 

there are a few limited exceptions.

Exception One:
Register #24 (Modbus Register #25) Drive Status, can also be read as a group of 6 words.

Exception Two:
AC Tech uses a method of reading a group of related registers that may not be consecutive within 
the drive memory map. When this is done for the registers below, the response from the drive will 
be for the number of words requested but will not be with consecutive registers.

Register #100 (Modbus Register #101), Fault history, should be read as a group of 4 words.
Register #101 (Modbus Register #102), Software version, should be read as a group of 4 words.

04  Read Input Registers (3X references). As with function 03, we read one register at a time except 

where noted.

Содержание AC Tech SC Series

Страница 1: ...SCF Series Drives Modbus Communications Reference Guide...

Страница 2: ...n of the drive 2003 Lenze AC Tech Corporation No part of this documentation may be copied or made available to third parties without the explicit written approval of Lenze AC Tech Corporation All info...

Страница 3: ...4 3 Data Representation Internal and External 5 3 1 Register Format 5 3 2 Data Types 5 3 3 AC Tech Drive Registers 5 4 SCF Drive Setup Operation 6 4 1 Serial Address 6 4 2 Serial Communications Parame...

Страница 4: ...mmand Source Registers 24 28 15 5 4 6 Auto Manual Status Registers 24 28 15 5 4 7 Present Fault Registers 24 29 16 5 4 8 Commanded Rotational Direction Registers 24 29 16 5 5 Motor Volts Register 30 1...

Страница 5: ...installing the drive controllers in machines commissioning i e the starting of operation as directed is prohibited until it is proven that the machine complies with the regulations of the EC Directiv...

Страница 6: ...entation DANGER After the controller has been disconnected from the supply voltage do not touch the live components and power connection until the capacitors have discharged Please observe the corresp...

Страница 7: ...g from 0 AC Tech register numbers are also numbered starting from 0 Therefore AC Tech register numbers always correspond exactly with the address transmitted As a result MODBUS REGISTER NUMBERS ARE AL...

Страница 8: ...he QC MC MCH SC TC smd Tmd and SMV Series drives support Modbus based communications Since each drive family has different parameters and size ranges the parameter register definitions are in many cas...

Страница 9: ...ries Internal Units Type Unit Example SPEED 1Hz 60Hz 600 TIME 1Sec 30 0Sec 300 3 3 AC Tech Drive Registers Registers 0 through 50 Modbus Registers 1 to 51 Reserved for configuration and control Regist...

Страница 10: ...9600 N 2 WITHOUT TIMER 4 9600 E 1 WITH TIMER 10 sec 5 9600 E 1 WITHOUT TIMER 6 9600 O 1 WITH TIMER 10 sec 7 9600 O 1 WITHOUT TIMER Explanation of Terms DISABLED serial link not operational WITH TIMER...

Страница 11: ...Control with bit 1 set will Lock both Controls and Parameters prevents writing to any register The serial drive control can be unlocked only if terminal TB1 is asserted and the drive is not in program...

Страница 12: ...tchdog using Programming Parameter 15 SERIAL LINK Programming Parameter 15 controls both the enabling of the serial link and the Watchdog By setting Parameter 15 to one of the selections WITH TIMER en...

Страница 13: ...d speed source to 01 keypad and put drive in MANUAL mode so that it responds to speed commands from the Keypad Speed Command register This is done by sending 0200 hex to Register 1 bit 9 asserted 4 Co...

Страница 14: ...D6L CRC 24 18 Command Speed R SA 03 00 18 00 01 CRC 0 2400 0 1 Hz 4a RS SA 03 02 DH DL CRC 25 19 Actual Speed R SA 03 00 19 00 01 CRC 0 2400 0 1 Hz 4b RS SA 03 02 DH DL CRC 26 1A Load DH Status DL R...

Страница 15: ...strates the Data High Byte and Data Low Byte format of Register 1 Drive Control Table 7 Drive Control Register 1 Data Low Byte 0 UPDATE BUFFERS 1 LOCK SECURITY 2 STOP DRIVE 3 START DRIVE 4 UNUSED 5 UN...

Страница 16: ...Hardware Configuration Register 22 Table 8 lists the SCF Drive Hardware Configuration Register 22 Bits 4 15 are not used at this time Table 8 Register 22 Drive Hardware Configuration BIT STATE MEANING...

Страница 17: ...oad D3H Operation Status D3L Rotational Direction D4H Control Mode D4L Speed Command Source D5L Auto Manual Status D5H Present Fault D6H Command Rotation D6L NOTE 4a Command Speed Bytes D1H and D1L or...

Страница 18: ...tional Direction Registers 24 27 Table 11 lists the Actual Rotational Direction Register 24 byte D4H or Register 27 DH Table 11 Actual Rotational Direction Setting Direction 0 FORWARD 1 REVERSE 5 4 4...

Страница 19: ...ter 28 DH Table 13 Speed Command Source Setting Source 0 KEYPAD 1 0 10VDC 2 4 20MA 3 PRESET 1 4 PRESET 2 5 PRESET 3 6 PRESET 4 7 PRESET 5 8 PRESET 6 9 PRESET 7 10 JOG 11 MOP 5 4 6 Auto Manual Status R...

Страница 20: ...ERNAL2 F2 12 INTERNAL3 F3 13 INTERNAL4 F4 14 INTERNAL5 F5 15 INTERNAL6 F6 16 INTERNAL7 F7 17 INTERNAL8 F8 18 INTERNAL9 F9 19 INTERNALo Fo 20 SINGLE PHASE FAULT SF 21 INCOMPATIBILITY FAULT cF 22 DYNAMI...

Страница 21: ...he drive sees no activity within the update time period it will stop the drive Whenever a communications session where 48 or 49was activated is to be ended register 1 bit 1 Lock Security must be asser...

Страница 22: ...ponse SA 03 08 D1H D1L D2H D2L D3H D3L D4H D4L CRC WRITING Message structure for writing 1 word all parameters Request SA 06 00 RA DH DL CRC Response SA 06 00 RA DH DL CRC LEGEND for Parameter List 1s...

Страница 23: ...rt 3 01 Normal 54 36H 4 Stop Method 01 Coast 02 Coast with DC Brake 03 Ramp 04 Ramp with DC Brake 01 Coast 55 37H 5 Speed Source 01 Keypad 02 Preset 1 03 0 10 VDC 04 4 20 mA 01 Keypad 56 38H 6 TB 14 O...

Страница 24: ...4 Preset Speed 2 05 Decrease Freq MOP 06 Jog Forward 07 Jog Reverse 08 Ramp to Stop 01 None 62 3EH 12 TB 13C Input 01 None 02 0 10 VDC 03 4 20 mA 04 Preset Speed 3 05 Inc Freq MOP 06 External Fault 07...

Страница 25: ...ncy Minimum Frequency 2400 240 0 Hz 600 60 0 Hz 75 4BH 25 Current Limit 300 1800 30 180 1800 180 76 4CH 26 Motor Overload 300 1000 30 100 1000 100 77 4DH 27 Base Frequency 250 5000 25 0 500 0 Hz 600 6...

Страница 26: ...H 50 FAULT HISTORY Must Read 4 Words Read Only See Note 5 101 65H 51 SOFTWARE VERSION Must Read 1 or 4 Words Read Only See Note 6 102 66H 52 BUS VOLTAGE 0 250 MIN 0 MAX 250 Read Only 103 67H 53 ACTUAL...

Страница 27: ...byte oldest fault is in the last data byte Refer to table 17 for clarification Table 17 Fault Codes Register 100 Code Fault Description Display 0 NO FAULT 1 OUTPUT TRANSISTOR FAULT OF 2 HIGH DRIVE TE...

Страница 28: ...number If received word contains hexadecimal number 0x4003 it translates to 0x40 decimal 64 software version and 0x03 decimal 3 revision number NOTE 7 AC Tech Registers 107 108 Parameter 57 58 Digital...

Страница 29: ...he timer is hard coded to a value of 10 seconds If the drive is under network control and the master does not communicate with the SCF drive for longer than the 10 second timeout period the drive will...

Страница 30: ...any other function 4 Setting the Drive to Manual Mode In order for the drive to respond to speed commands written to the keypad speed register the drive must be put into manual mode To do this write...

Страница 31: ...tatus byte D3L or Register 26 DL VALUE OPERATIONAL STATE 0 FAULT LOCKOUT 1 FAULT 2 START PENDING 3 STOP 4 DC BRAKE 5 RUN AT 0Hz 6 RUN 7 ACCEL 8 DECEL 9 CURRENT LIMIT 10 DECEL OVERRIDE 11 LOWER TRANSIS...

Страница 32: ...Lenze AC Tech Corporation 630 Douglas Street Uxbridge MA 01569 USA Sales 800 217 9100 Service 508 278 9100 www lenze actech com RG SFMOD e6...

Отзывы: