Electrical installation
Mounting steps
EDK82ZM113−001 DE/EN/FR 1.1
39
l
H1_E_INST−Verdraht_EE2ZM−001
Mounting steps
2
1
0
3
E82ZM−005
How to connect the interference suppression module:
1. De−energise the control cabinet and fuse it against re−energisation.
2. Wait for at least 3 minutes before checking the standard device for isolation from
supply.
3. Connect the connecting cable of the motor interference suppression module
0
to the
terminals of the standard device (U, V, W, and PE).
– Observe the documentation of the standard device!
4. Apply the motor cable.
– Apply the motor cable to the terminals U’, V’, W’
1
and to the PE screw
2
,
respectively.
– Apply the motor cable shielding extensively to the shield connection on the right
hand side and fix it using the shield clamp
3
(included in the scope of supply).