36
RackSwitch G8052 Installation Guide
To install the G8052 in a standard equipment rack, complete the following steps:
1. Locate, record, and retain the product switch information in order to configure
and register your product. See
“Recording Important Product Information” on
page 30
.
Note:
If this switch is a replacement switch, copy the product information from the
original switch onto the RID label that is shipped with replacement switch
and affix the new label to the bottom of the new switch.
2. Use the M4 screws to attach a mounting bracket to each side of the switch.
Torque the screws to approximately 2.0 newton-meters (Nm) ± 0.1 Nm (17.7
inch-pounds).
3. Slide the switch into the rack.
4. Use M6 screws, washers, and clip nuts (or cage nuts) to secure the switch unit
to the rack. Torque the screws to approximately 5.7 Nm ± 0.1 Nm (50
inch-pounds).
5. If installing the 1U air duct option, see the instruction on
page 44
.
6. Connect all external cables in accordance with the
“Cabling Guidelines” on
page 34
.