Lennox XC15-024 Скачать руководство пользователя страница 6

Page 6

505095M 1/3/06

Refrigerant Piping

If the XC15 unit is being installed with an indoor coil and line
set, make the refrigerant connections as outlined in this
section. f an existing line set and/or indoor coil is going to
be used to complete the XC15 system, refer to this section,
as well as the flushing section which follows.

Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections). Use Lennox L15 (sweat, non−
flare) series line sets as shown in table 2 or use field−fabri-
cated refrigerant lines. Valve sizes are also listed in table 2.

Table 2

Refrigerant Line Sets

Valve Sizes

Recommended Line Set

Model

Liquid
Line

Vapor
Line

Liquid
Line

Vapor
Line

L15
Line Sets

−024
−030
−036

3/8 in.
(10 mm)

3/4 in.
(19 mm)

3/8 in
(10 mm)

3/4 in.
(19 mm)

L15−41
15 − 50 ft.
(5 − 15 m)

−042
−048

3/8 in.
(10 mm)

7/8 in
(22 mm)

3/8 in.
(10 mm)

7/8in
(22 mm)

L15−65
15 − 50 ft.
(5 − 15m)

−060

3/8 in.
(10 mm)

1−1/8 in.
(29 mm)

3/8 in.
(10 mm)

1−1/8 in.
(29 mm)

Field
Fabricated

NOTE − When installing refrigerant lines longer than 50
feet, contact Lennox Technical Support Product
Applications for assistance. To obtain the correct
information from Lennox, be sure to communicate the
following points:

S

Line set diameters for the unit being installed (from
table 2)

S

Model (XC15) and size of unit (e.g. −060).

IMPORTANT

Matching XC15 with new Indoor Coil and Line
SetIf an existing indoor coil equipped with an
RFCI metering device is being replaced, also install
a new liquid line prior to installing the XC15 unit.

Installing Refrigerant Line

If refrigerant lines are routed through a wall, seal and iso-
late the opening so vibration is not transmitted to the build-
ing. Pay close attention to line set isolation during installa-
tion of any HVAC system. When properly isolated from
building structures (walls, ceilings. floors), the refrigerant
lines will not create unnecessary vibration and subsequent
noises. Also, consider the following when placing and
installing a high−efficiency outdoor unit:

1.

Placement

Some localities are adopting sound ordi-

nances based on the unit’s noise level registered  from
the adjacent property, not from the installation proper-
ty. Install the unit as far as possible from the property
line. When possible, do not install the unit directly out-
side a window. Glass has a very high level of sound
transmission (see figure 8).

Install unit

away from

windows

Two 90° elbows installed in line
set will reduce line set vibration.

Figure 8

Outside Unit Placement and Installation

2.

Line Set Isolation

The following illustrations dem-

onstrate procedures which ensure proper refrigerant
line set isolation. Figure 10 shows how to install line
sets on horizontal runs. Figure 11 shows how to make
a transition from horizontal to vertical. Figure 12 shows
how to install line sets on vertical runs.

Installing Isolation Grommets

Locate the isolation grommets (provided). Slide grommets
onto vapor and liquid lines. Insert grommets into mullion to
isolate refrigerant lines from sheet metal edges.

WARNING

Polyol ester (POE) oils used with R−410A refriger-
ant absorb moisture very quickly. It is very impor-
tant that the refrigerant system be kept closed as
much as possible. DO NOT remove line set caps or
service valve stub caps until you are ready to make
connections.

Содержание XC15-024

Страница 1: ...low voltage wiring 2 Grommets for liquid and vapor lines Check equipment for shipping damage If you find any damage immediately contact the last carrier INSTALLATION INSTRUCTIONS XC15 Series Units CON...

Страница 2: ...UND REDUCTION COVER SEE PAGE 20 FOR COVER INFORMATION COMPRESSOR TERMINAL PLUG HIGH PRESSURE SWITCH Figure 1 37 940 024 thru 042 47 1194 048 and 060 21 1 8 537 024 thru 042 31 1 8 791 048 and 060 10 3...

Страница 3: ...NG This product and or the indoor unit it is matched with may contain fiberglass wool Disturbing the insulation during installation main tenance or repair will expose you to fiberglass wool dust Breat...

Страница 4: ...uide the LIP of top tab inward fig ure 5 Details A and C then upward into the top slot of the hinge corner post S Rotate panel to vertical to fully engage all tabs S Holding the panel s hinged side fi...

Страница 5: ...for field wiring diagram A complete unit wiring dia gram is located on the back side of the access panel NOTE For proper voltages select thermostat wire gauge per the following chart Wire run length A...

Страница 6: ...Refrigerant Line If refrigerant lines are routed through a wall seal and iso late the opening so vibration is not transmitted to the build ing Pay close attention to line set isolation during installa...

Страница 7: ...for use with R 410A refriger ant While brazing in the line set connections wrap a wet cloth around the valve body and the copper tube stubs 4 Quench the joints with a wet cloth to prevent possible he...

Страница 8: ...LIQUID LINE Refrigerant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE...

Страница 9: ...maintenance service repair and disposal of appliance Approved methods of recovery recycl ing or reclaiming must be followed 1 Remove existing R 22 refrigerant using the following appropriate procedure...

Страница 10: ...liquid refrigerant to flow into the system through the vapor line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machi...

Страница 11: ...Schrader valve from contamination and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is...

Страница 12: ...the manifold gauge set Open the valve on the R 410A cylinder va por only 3 Open the high pressure side of the manifold to allow R 410A into the line set and indoor unit Weigh in a trace amount of R 4...

Страница 13: ...frozen bearings or binding 2 Inspect all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and vapor line service valves to release the refri...

Страница 14: ...arge If weighing facili ties are not available or if charging the unit during warm weather use one of the following procedures Charge Using the Approach Method Outdoor Temp 65 F 18 C The following pro...

Страница 15: ...results use the same electronic thermometer to check both outdoor ambient and liquid line temperatures F 1 0 C 0 5 1 With the manifold gauge hose still on the liquid service port and the unit operatin...

Страница 16: ...0 psi Filter Drier A drier is factory installed in each XC15 unit A replace ment drier is available from Lennox Refer to Lennox Re pair Part Program System Operation Monitor LSOM The diagnostic indica...

Страница 17: ...not present R and C wires are reversed Thermostat demand signal Y1 is present but compres sor not running 1 Compressor protector is open 2 Outdoor unit power disconnect is open 3 Compressor circuit br...

Страница 18: ...is connect switch es Unit may have multiple power supplies Maintenance and service must be performed by a qualified installer or service agency At the beginning of each cool ing season check the syste...

Страница 19: ...m call your Lennox dealer for assistance IMPORTANT Turn off electrical power to the unit at the disconnect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable...

Страница 20: ...tch from heating mode to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature Programmable Thermostats Your Lenn...

Отзывы: