background image

Page 3

XC15 SERIES

*A service clearance of 30" (762 mm) must be maintained on
the access panel side of the unit. Clearance to one of the oth-
er three sides must be 36" (914 mm). Clearance to one of the
remaining two sides may be 12" (304 mm) and the final side
may be 6" (152 mm).

A clearance of 24" (610 mm) must be maintained between
two units.  48" (1219 mm) clearance required on top of unit.
Maximum soffit overhang is 36" (914 mm).

Installation Clearances

Figure 2

(as
noted)

30 in. (762−mm)

(as noted)

(as
noted)

Slab Mounting

When installing a unit at grade level, the top of the slab
should be high enough above the grade so that water from
higher ground would not collect around the unit. See figure
3. Slab may be level or have a slope tolerance away from
the building of not more than 2 degrees or 2 inches per 5
feet (51 mm per 1524 mm).

INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2
DEGREES (OR 2 INCHES PER 5 FEET [51 MM PER 1.5 M]) AWAY FROM
BUILDING STRUCTURE.

Slab Mounting At Ground Level

MOUNTING
SLAB

BUILDING
STRUCTURE

Figure 3

Roof Mounting

Install unit at a minimum of 4 inches above the surface of
the roof. Care must be taken to ensure weight of unit is
properly distributed over roof joists and rafters. Either red-
wood or steel supports are recommended.

Removing Panels

WARNING

This product and/or the indoor unit it is matched
with may contain fiberglass wool.

Disturbing the insulation during installation, main-
tenance, or repair will expose you to fiberglass wool
dust. Breathing this may cause lung cancer. (Fiber-
glass wool is known to the State of California to
cause cancer.)

Fiberglass wool may also cause respiratory, skin,
and eye irritation.

To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact
your supervisor.

Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900

CAUTION

To prevent personal injury, or damage to panels,
unit or structure, be sure to observe the following:

While installing or servicing this unit, carefully stow
all removed panels out of the way, so that the panels
will not cause injury to personnel, nor cause dam-
age to objects or structures nearby, nor will the pan-
els be subjected to damage (e.g., being bent or
scratched).

While handling or stowing the panels, consider any
weather conditions, especially windy conditions,
that may cause panels to be blown around and bat-
tered.

Access Panel

WARNING

Unit must be grounded in accordance
with national and local codes.  Elec-
tric Shock Hazard.  Can cause injury
or death.

Line voltage is present at all compo-
nents when unit is not in operation on
units with single-pole contactors. Dis-
connect all remote electric power sup-
plies before opening access panel.
Unit may have multiple power sup-
plies.

Содержание XC15-024

Страница 1: ...low voltage wiring 2 Grommets for liquid and vapor lines Check equipment for shipping damage If you find any damage immediately contact the last carrier INSTALLATION INSTRUCTIONS XC15 Series Units CON...

Страница 2: ...UND REDUCTION COVER SEE PAGE 20 FOR COVER INFORMATION COMPRESSOR TERMINAL PLUG HIGH PRESSURE SWITCH Figure 1 37 940 024 thru 042 47 1194 048 and 060 21 1 8 537 024 thru 042 31 1 8 791 048 and 060 10 3...

Страница 3: ...NG This product and or the indoor unit it is matched with may contain fiberglass wool Disturbing the insulation during installation main tenance or repair will expose you to fiberglass wool dust Breat...

Страница 4: ...uide the LIP of top tab inward fig ure 5 Details A and C then upward into the top slot of the hinge corner post S Rotate panel to vertical to fully engage all tabs S Holding the panel s hinged side fi...

Страница 5: ...for field wiring diagram A complete unit wiring dia gram is located on the back side of the access panel NOTE For proper voltages select thermostat wire gauge per the following chart Wire run length A...

Страница 6: ...Refrigerant Line If refrigerant lines are routed through a wall seal and iso late the opening so vibration is not transmitted to the build ing Pay close attention to line set isolation during installa...

Страница 7: ...for use with R 410A refriger ant While brazing in the line set connections wrap a wet cloth around the valve body and the copper tube stubs 4 Quench the joints with a wet cloth to prevent possible he...

Страница 8: ...LIQUID LINE Refrigerant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE...

Страница 9: ...maintenance service repair and disposal of appliance Approved methods of recovery recycl ing or reclaiming must be followed 1 Remove existing R 22 refrigerant using the following appropriate procedure...

Страница 10: ...liquid refrigerant to flow into the system through the vapor line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machi...

Страница 11: ...Schrader valve from contamination and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is...

Страница 12: ...the manifold gauge set Open the valve on the R 410A cylinder va por only 3 Open the high pressure side of the manifold to allow R 410A into the line set and indoor unit Weigh in a trace amount of R 4...

Страница 13: ...frozen bearings or binding 2 Inspect all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and vapor line service valves to release the refri...

Страница 14: ...arge If weighing facili ties are not available or if charging the unit during warm weather use one of the following procedures Charge Using the Approach Method Outdoor Temp 65 F 18 C The following pro...

Страница 15: ...results use the same electronic thermometer to check both outdoor ambient and liquid line temperatures F 1 0 C 0 5 1 With the manifold gauge hose still on the liquid service port and the unit operatin...

Страница 16: ...0 psi Filter Drier A drier is factory installed in each XC15 unit A replace ment drier is available from Lennox Refer to Lennox Re pair Part Program System Operation Monitor LSOM The diagnostic indica...

Страница 17: ...not present R and C wires are reversed Thermostat demand signal Y1 is present but compres sor not running 1 Compressor protector is open 2 Outdoor unit power disconnect is open 3 Compressor circuit br...

Страница 18: ...is connect switch es Unit may have multiple power supplies Maintenance and service must be performed by a qualified installer or service agency At the beginning of each cool ing season check the syste...

Страница 19: ...m call your Lennox dealer for assistance IMPORTANT Turn off electrical power to the unit at the disconnect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable...

Страница 20: ...tch from heating mode to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature Programmable Thermostats Your Lenn...

Отзывы: