background image

Page 15

XC15 SERIES

Table 5

XC15 Normal Operating Pressures In psig (/− 10 and vapor+/− 5 PSIG)*

Model

−024

−030

−036

−042

−048

−060

 

5

F (

5

C)**

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

65 (18.3)

239

135

246

135

245

132

260

132

224

129

242

131

70 (21.1)

255

136

266

136

264

133

282

133

241

130

262

132

75 (23.9)

274

137

285

138

285

135

302

134

259

131

282

134

80 (26.7)

293

138

306

139

306

137

325

135

279

133

303

135

85 (29.4)

317

139

328

140

328

137

347

136

301

134

326

136

90 (32.2)

339

140

350

141

352

139

370

137

323

135

349

137

95 (35.0)

362

141

374

142

375

140

395

138

347

137

372

138

100 (37.8)

387

142

399

143

400

141

421

139

372

138

397

140

105 (40.6)

415

144

423

144

425

141

446

141

397

140

422

141

110 (43.3)

440

145

450

145

452

143

475

142

422

141

448

143

115 (46.1)

469

146

477

146

476

144

504

144

449

143

475

146

*

These are typical pressures only. Indoor match up, indoor air quality, and indoor load will cause the pressures to vary.

** Temperature of air entering outdoor coil.

Charge Using Subcooling Method

Outdoor Tem-

perature > 65ºF (18ºC) 

Use the following method to obtain accurate subcooling
values. Compare the measured subcooling value to the
values given in table 6.

Table 6

XC15 Subcooling Values

(psig

)

_

Saturation Temperature

_

Liquid Line Temperature

=

_

Subcooling Value

Model

−024

−030

−036

−042

−048

−060

°F

(°C)*

4

(2.2)

4

(2.2)

6

(3.3)

7

(3.9)

6

(3.3)

7

(3.9)

NOTE − For best results, use the same electronic thermometer to
check both outdoor-ambient and liquid-line temperatures.
*F: +/−1.0°; C: +/−0.5°

1. With the manifold gauge hose still on the liquid service

port and the unit operating stably, use a digital ther-
mometer to record the 

liquid line temperature

 in the

space provided in table 6, and at the same time, record
the 

liquid line pressure

 reading in the (psig___)"

space in the table.

2. Use a temperature/pressure chart for R−410A (table 7)

to determine the 

saturation temperature

 for the liq-

uid line pressure reading and record that in the space
provided in table 6.

3. Subtract the liquid line temperature from the saturation

temperature (according to the chart) to determine the

subcooling value

.

4. Compare subcooling value with those in table 6. If sub-

cooling is greater than shown, recover some refriger-
ant; if less than shown, add some refrigerant.

Charge using Subcooling Method

Outdoor Tem-

perature < 65ºF (18ºC) 

When the outdoor ambient temperature is below 65°F
(18°C), use the subcooling method to charge the unit. It
may be necessary to restrict the air flow through the out-
door coil to achieve pressures in the 325−375 psig
(2240−2585 kPa) range. These higher pressures are nec-
essary for checking the charge. Block equal sections of air
intake panels and move obstructions sideways until the liq-
uid pressure is in the 325−375 psig (2240−2585 kPa) range.
See figure 17.

Blocking Outdoor Coil

*Outdoor coil should be blocked one
side at a time with cardboard or plastic
sheet until proper testing pressures
are reached.

cardboard or plastic sheet

*Four−sided unit shown.

Figure 17

Содержание XC15-024

Страница 1: ...low voltage wiring 2 Grommets for liquid and vapor lines Check equipment for shipping damage If you find any damage immediately contact the last carrier INSTALLATION INSTRUCTIONS XC15 Series Units CON...

Страница 2: ...UND REDUCTION COVER SEE PAGE 20 FOR COVER INFORMATION COMPRESSOR TERMINAL PLUG HIGH PRESSURE SWITCH Figure 1 37 940 024 thru 042 47 1194 048 and 060 21 1 8 537 024 thru 042 31 1 8 791 048 and 060 10 3...

Страница 3: ...NG This product and or the indoor unit it is matched with may contain fiberglass wool Disturbing the insulation during installation main tenance or repair will expose you to fiberglass wool dust Breat...

Страница 4: ...uide the LIP of top tab inward fig ure 5 Details A and C then upward into the top slot of the hinge corner post S Rotate panel to vertical to fully engage all tabs S Holding the panel s hinged side fi...

Страница 5: ...for field wiring diagram A complete unit wiring dia gram is located on the back side of the access panel NOTE For proper voltages select thermostat wire gauge per the following chart Wire run length A...

Страница 6: ...Refrigerant Line If refrigerant lines are routed through a wall seal and iso late the opening so vibration is not transmitted to the build ing Pay close attention to line set isolation during installa...

Страница 7: ...for use with R 410A refriger ant While brazing in the line set connections wrap a wet cloth around the valve body and the copper tube stubs 4 Quench the joints with a wet cloth to prevent possible he...

Страница 8: ...LIQUID LINE Refrigerant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE...

Страница 9: ...maintenance service repair and disposal of appliance Approved methods of recovery recycl ing or reclaiming must be followed 1 Remove existing R 22 refrigerant using the following appropriate procedure...

Страница 10: ...liquid refrigerant to flow into the system through the vapor line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machi...

Страница 11: ...Schrader valve from contamination and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is...

Страница 12: ...the manifold gauge set Open the valve on the R 410A cylinder va por only 3 Open the high pressure side of the manifold to allow R 410A into the line set and indoor unit Weigh in a trace amount of R 4...

Страница 13: ...frozen bearings or binding 2 Inspect all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and vapor line service valves to release the refri...

Страница 14: ...arge If weighing facili ties are not available or if charging the unit during warm weather use one of the following procedures Charge Using the Approach Method Outdoor Temp 65 F 18 C The following pro...

Страница 15: ...results use the same electronic thermometer to check both outdoor ambient and liquid line temperatures F 1 0 C 0 5 1 With the manifold gauge hose still on the liquid service port and the unit operatin...

Страница 16: ...0 psi Filter Drier A drier is factory installed in each XC15 unit A replace ment drier is available from Lennox Refer to Lennox Re pair Part Program System Operation Monitor LSOM The diagnostic indica...

Страница 17: ...not present R and C wires are reversed Thermostat demand signal Y1 is present but compres sor not running 1 Compressor protector is open 2 Outdoor unit power disconnect is open 3 Compressor circuit br...

Страница 18: ...is connect switch es Unit may have multiple power supplies Maintenance and service must be performed by a qualified installer or service agency At the beginning of each cool ing season check the syste...

Страница 19: ...m call your Lennox dealer for assistance IMPORTANT Turn off electrical power to the unit at the disconnect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable...

Страница 20: ...tch from heating mode to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature Programmable Thermostats Your Lenn...

Отзывы: