background image

9

Wiring Connections

In the U.S.A., wiring must conform with current local 

codes and the current National Electric Code (NEC). In 

Canada, wiring must conform with current local codes 

and the current Canadian Electrical Code (CEC). 
Refer to unit nameplate for minimum circuit ampacity and 

maximum overcurrent protection size. 

1.  Lift indoor unit front panel to access the control 

box  over.  Remove  the  screw(s)  securing  the  cover. 

Remove the plate.

2.  Locate the terminal strip in the control box. Connect 

the power wiring (sized per NEC/CEC and local 

codes) and communications cable 

(three-conductor, 

shielded cable).

 Refer to unit nameplate for rated 

voltage.

3.  If the indoor unit is the final unit in a group that is wired 

in series, install the provided resistor across terminals 

P and Q. 

4.  Remove spacer. Secure bottom of unit to wall mounting 

bracket. Continue with installation of outdoor unit and 

system commissioning.

CONTROL BOX

COVER

L1 L2

POWER WIRING

COMMUNICATION

WIRING

VWMB007H4, VWMB009H4, VWMB012H4, 

VWMB015H4, VWMB018H4

VWMB024H4, VWMB030H4

POWER WIRING

COMMUNICATION

WIRING

CONTROL BOX

COVER

Figure 11. Accessing Control Box

Capacity

Brand

Model 

Name

Model #  Cat #

Max Flow 

Rate 

(gal per hr)

Max  

head (ft.)

Max  

suction  

lift*

VWMB007H4 - VWMB018H4

Blue  

Diamond

MicroBlue  X85-003  14T74 

1.3

16

6 ft

VWMB007H4 - VWMB018H4

MicroBlue 

Fascia Kit

T18-016 17A24

-

-

-

VWMB024H4 - VWMB030H4

MaxiBlue 

w Reservoir X87-721  14T69 

3.7

23

16.5 ft

VWMB024H4 - VWMB030H4

MaxiBlue 

w DrainStik

X87-722   17A23 

3.7

23

16.5 ft

*Optional pump maximum suction lift is measured from the pump outlet.

Table 3. Condensate Pump Accessory Options

NOTE -

 Two-conductor shielded cable must be used for 

the communication wiring. This is necessary to 

ensure 

proper system communication and operation.

 WARNING

Isolate the power supply before accessing unit electrical 

terminals.

Install unit so that unit disconnect is accessible.

Follow all local and national codes, as well as this 

installation instruction, during installation. Do NOT 

overload electrical circuit, as this may lead to failure and 

possible fire.

Use  specified  wiring  and  cable  to  make  electrical 

connections. Clamp cables securely and make sure that 

connections are tight to avoid strain on wiring. Insecure 

wiring connections may result in equipment failure and 

risk of fire. 

Wiring must be installed so that all cover plates can be 

securely closed.

 CAUTION

This unit must be properly grounded and protected by a 

circuit breaker. The ground wire for the unit must not be 

connected to a gas or water pipe, a lightning conductor 

or a telephone ground wire. 

Do not connect power wires to the outdoor unit until 

all other wiring and piping connections have been 

completed.

Install all wiring at least 3 feet away from televisions,  

radios or other electronic devices in order to avoid the 

possibility of interference with the unit operation.

Do not install the unit near a lighting appliance that 

includes a ballast. The ballast may affect remote control 

operation.

Содержание VRF VWMB Series

Страница 1: ...injury or loss of life Installation and service must be performed by a li censed professional HVAC installer service agency or the gas supplier Failure to follow safety warnings and these instruc tio...

Страница 2: ...se of a different rating Do not use a jumper wire to replace a fuse Do not insert your hands tools or any other item into the air intake or air outlet at either the indoor or outdoor unit Do not allow...

Страница 3: ...879 39 991 12 3 8 314 7 1 2 191 4 1 2 114 VWMB007H4 VWMB009H4 VWMB012H4 VWMB015H4 VWMB018H4 27 686 BOTTOM VIEW SIDE VIEW SIDE VIEW 8 7 8 225 42 1 2 1080 47 1194 13 1 2 343 10 3 8 264 VWMB024H4 VWMB030...

Страница 4: ...t of the unit Install the indoor unit a minimum of 3 feet away from any antenna power cord line radio telephone security system or intercom Electrical interference and radio frequencies from any of th...

Страница 5: ...e installed level on the wall to allow proper condensate drainage 1 Use a carpenter s level or measuring tape to verify the wall mounting plate is horizontally level 2 Secure the wall mounting plate t...

Страница 6: ...of copper pipe and wiring can deteriorate when exposed to these construction materials USE SUITABLE TOOL TO CUT PVC FOR WALL SLEEVE AT SLIGHT ANGLE AS SHOWN Figure 4 Cutting PVC for Wall Sleeve Insta...

Страница 7: ...connections should always be accessible and must be insulated to prevent condensation 9 After refrigerant piping has been installed and checked for leaks apply insulation over the connector pipe and a...

Страница 8: ...ll drain freely 4 After system installation is complete the condensate drain line must be checked for leaks This check is part of the commissioning sequence If a field provided condensate pump has bee...

Страница 9: ...X87 721 14T69 3 7 23 16 5 ft VWMB024H4 VWMB030H4 MaxiBlue w DrainStik X87 722 17A23 3 7 23 16 5 ft Optional pump maximum suction lift is measured from the pump outlet Table 3 Condensate Pump Accessory...

Страница 10: ...tdoor Unit Main Unit L1 L2 L3 Outdoor Unit Sub1 unit L1 L2 L3 Outdoor Unit Sub2 Unit L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 Service Disconnect Service Disconnect Service Discon...

Страница 11: ...olarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor Un...

Страница 12: ...agram VRF Heat Pump System NOTE PQE Communication wiring is daisy chained from the outdoor unit to each indoor unit in one continuous run Tightening torque for the terminal screws Use the correct scre...

Страница 13: ...WIRING Display panel To Outdoor COMM BUS To wired Controller COMM BUS HA HB COM P 12V Q GRAY YELLOW BLUE WHITE BLACK RED HHE interface FAN CTON HTON AUXH NET0 NET1 Current range 0 1A Voltage range 0...

Страница 14: ...HITE BLACK RED NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING NOTE 1 REFER TO MANUAL FOR COMMUNICATION WIRING 2 PLEASE USE THE 3 CONDUCTOR SHIELDED CABLE T2A T2 T1 T2B RED WHITE BLUE BLACK Di...

Страница 15: ...le Spot Check Instructions This Spot Check Performance table is located on the unit service panel The diagnostic information can also be obtained using the wired remote controller No Content Recorded...

Страница 16: ...codes The error code will replace the temperature setting displayed on the receiver If more than one error has occurred the codes will alternate so that all codes are shown Figure 32 Receiver Display...

Страница 17: ...17 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Отзывы: