5
Determining Wall Mounting Plate Location
1. Remove the wall mounting plate from the back of the
indoor unit.
2. Determine the best exit location for utility bundle (line
set, condensate line and wiring).
3. Position the wall mounting plate on the wall so that,
when installed, the unit will be at least 6 inches (152
mm) from the ceiling and 5 inches (127 mm) from the
wall on either side. The wall mounting plate must be
level side-to-side.
4. Use the wall mounting plate as a template to determine
the exit point for utility bundle. Mark the wall to facilitate
drilling hole for utility bundle.
Right piping
Left piping
Right back piping
Left back piping
Figure 1. Determining Exit Locations
Installation
Wall Mounting Plate Installation
Install the wall mounting plate so that it is correctly
positioned horizontally and vertically. The indoor unit must
be installed level on the wall to allow proper condensate
drainage.
1. Use a carpenter's level or measuring tape to verify the
wall mounting plate is horizontally level.
2. Secure the wall mounting plate to the wall using the
provided screws and screw anchors. NOTE - It is
important to use all screws provided to secure the wall
mounting plate to the wall. Additional holes may be
drilled through the metal wall mounting plate to better
secure wall plate. Field-provided anchors/fixings may
be required depending on wall construction. Use the
appropriate type of anchors for the application.
3. The wall mounting plate must be installed flush
against the wall so that the indoor unit will be flush
after installation. Any space between the wall and unit
will cause noise and vibration.
4. The wall mounting plate must be installed horizontally
level on the wall.
Figure 2. Wall Mounting Brackets
VWMB024H4, VWMB030H4
Outline of Indoor Unit
Wall Mounting Bracket
Outline of Indoor Unit
Wall Mounting Bracket
VWMB007H4, VWMB009H4, VWMB012H4, VWMB015H4, VWMB018H4