19
Outdoor Model
Gas pipe size mm(in.)
Liquid pipe size mm(in.)
VEP648N432K
Φ51.4(2)
Φ25.4(1)
VEP669N432K
Φ51.4(2)
Φ25.4(1)
VEP690N432K
Φ51.4(2)
Φ25.4(1)
VEP708N432K
Φ51.4(2)
Φ25.4(1)
VEP726N432K
Φ51.4(2)
Φ25.4(1)
VEP750N432K
Φ51.4(2)
Φ25.4(1)
VEP762N432K
Φ51.4(2)
Φ25.4(1)
VEP780N432K
Φ51.4(2)
Φ25.4(1)
VEP801N432K
Φ51.4(2)
Φ25.4(1)
VEP822N432K
Φ51.4(2)
Φ25.4(1)
VEP840N432K
Φ51.4(2)
Φ25.4(1)
③
. If the length between an IDU and its nearest branch is above 10m(32-4/5ft.), then
increase the size of the liquid pipe of IDU (only for the pipe size that
is≤6.35mm(1/4in.).
4.2.4 Connection Pipe among Outdoor Modules
Unit: m (ft.)
Fig.23
Unit: m (ft.)
Fig.24
NOTICE!
When the distance between outdoor units exceeds 2m(6-1/2ft.), U-type oil trap
should be added at low pressure gas pipe. a+c≤10m(32-7/8ft.);b+c≤10m(32-7/8ft.);d≤10m
(32-7/8ft.).