background image

Page 37

CBX32MV SERIES

S

The outdoor unit should come on immediately and the
indoor blower should start between 30 − 60 seconds
later.

S

Check the airflow from a register to confirm that the
system is moving cooled air.

S

Set the thermostat 5ºF higher than the indoor
temperature. The indoor blower and outdoor unit
should cycle off.

CHECK ELECTRIC HEATER (IF USED)

S

Set thermostat to call for auxiliary heat (approximately
5°F above ambient temperature). The indoor blower
and auxiliary heat should come on together. Allow a
minimum of 3 minutes for all sequencers to cycle on.

S

Set the thermostat so that it does not call for heat.
Allow up to 5 minutes for all sequencers to cycle off.

Operation

COOLING (COOLING ONLY OR HEAT PUMP)

When the thermostat calls for cooling, 24 volts is put on the
blower time−delay relay coil. After a delay, the indoor
blower relay energizes. The normally open contacts close,
causing the indoor blower motor to operate. The circuit
between R and Y is completed, closing the circuit to the
contactor in the outdoor unit, starting the compressor and
outdoor fan motor.

On heat pumps, circuit R and O energizes the reversing
valve, switching the valve to the cooling position. (The
reversing valve remains energized as long as the
thermostat selector switch is in the COOL position.)

At the completion of the cooling demand and after the
relay’s time-delay, the compressor and outdoor fan will
cycle off.

HEATING (ELECTRIC HEAT ONLY)

When the thermostat calls for heat, the circuit between R
and W is completed, and the heat sequencer is energized.
A time delay follows before the heating elements and the
indoor blower motor come on. Units with a second heat
sequencer can be connected with the first sequencer to W
on the thermostat subbase, or they may also be connected
to a second stage on the subbase.

HEATING (HEAT PUMP)

When the thermostat calls for heating, 24 volts is put on the
blower time−delay relay coil. After a delay, the normally
open contacts close, causing the indoor blower motor to
operate. The circuit between R and Y is completed, closing
the circuit to the contactor in the outdoor unit, starting the
compressor and outdoor fan motor.  Circuit R and G
energizes the blower relay, starting the indoor blower
motor.

If the room temperature should continue to fall, the circuit
between R and W1 is completed by the second-stage heat
room thermostat. Circuit R−W1 energizes a heat
sequencer. The completed circuit will energize
supplemental electric heat (if applicable). Units with a

second heat sequencer can be connected with the first
sequencer to W1 on the thermostat. They may also be
connected to a second heating stage W2 on the thermostat
subbase.

EMERGENCY HEAT (HEATING HEAT PUMP)

If the selector switch on the thermostat is set to the
emergency heat position, the heat pump will be locked out
of the heating circuit, and all heating will be electric heat (if
applicable). A jumper should be placed between W2 and E
on the thermostat subbase so that the electric heat control
will transfer to the first-stage heat on the thermostat. This
will allow the indoor blower to cycle on and off with the
electric heat when the fan switch is in the AUTO position.

Maintenance

DEALER

WARNING

Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at disconnect
switch(es). Unit may have multiple power
supplies.

WARNING

Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.

Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:

Outdoor Unit

1. Outdoor unit fan motor is pre−lubricated and sealed.

No further lubrication is needed.

2. Visually inspect all connecting lines, joints and coils for

evidence of oil leaks.

3. Check all wiring for loose connections.
4. Check for correct voltage at unit (unit operating).
5. Check amp draw on outdoor fan motor.

Motor

 

Nameplate

:_________ 

Actual

:__________.

6. Inspect drain holes in coil compartment base and

clean if necessary.

NOTE - If insufficient cooling occurs, the unit should be
gauged and refrigerant charge should be checked.

Outdoor Coil

Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.

NOTE  It may be necessary to flush the outdoor coil
more frequently if it is exposed to substances which are
corrosive or which block airflow across the coil (e.g., pet
urine, cottonwood seeds, fertilizers, fluids that may contain
high levels of corrosive chemicals such as salts)

Содержание Variable Speed Air Handlers CBX32MV

Страница 1: ...HANDLER 506274 01 06 11 Supersedes 01 11 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Table of Contents Shipping and Packing List 1 Upflow Downflow Unit Dimensions 2 Horizontal LH RH Unit Dimensions...

Страница 2: ...5 8 16 5 8 16 LOW VOLTAGE RIGHT SIDE LINE VOLTAGE LEFT SIDE DOWNFLOW POSITION 1 25 UPFLOW POSITION CONDENSATE DRAINS 2 UPFLOW AND DOWNFLOW FILTER ACCESS FILTER ACCESS H G H G LINE VOLTAGE INLETS TOP...

Страница 3: ...SIDE 5 3 8 137 4 3 8 111 LIQUID LINE SUCTION LINE SUPPLY AIR OPENING FILTER LOW VOLTAGE INLETS TOP AND LEFT SIDE END VIEW BLOWER B C D COIL 3 4 19 3 4 19 3 4 19 RETURN AIR OPENING F E 5 8 16 5 8 16 5...

Страница 4: ...jurisdiction before installation Check equipment for shipping damage if found immediately report damage to the last carrier Installation Clearances Cabinet 0 inch 0 mm To Plenum 1 inch 25 mm To Outlet...

Страница 5: ...embled to facilitate setting the unit Follow the steps below To disassemble 1 Remove access panels 2 Remove both blower and coil assemblies This will lighten the cabinet for lifting 3 Remove one screw...

Страница 6: ...HIGH HUMIDITY AREAS For horizontal applications in high humidity areas remove the downflow rail closest to the drain pan To remove rail 1 Remove the screws from the rail at the back of unit and at th...

Страница 7: ...d in figure 4 detail A 5 Remove horizontal drip shield screw located in the left center of the back coil end seal as illustrated in figure 4 detail A 6 Rotate horizontal drip shield 180 front to back...

Страница 8: ...zontal drip shield from the corrugated padding between the blower and coil assembly NOTE Discard the corrugated padding and the downflow drip shields from the foam pads on top of the unit The shields...

Страница 9: ...ownflow Combustible Base Dimensions Brazing Connections WARNING Polyol ester POE oils used with HFC 410A refrigerant absorb moisture very quickly It is very important that the refrigerant system be ke...

Страница 10: ...NOTE REFRIGERANT LINE SETS SHOULD BE ROUTED TO ALLOW FILTER ACCESSIBILITY NOTE CBX32MV SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVE...

Страница 11: ...o debris has fallen into the drain pan during installation that may plug up the drain opening MAIN DRAIN Connect the main drain and route downward to drain line or sump Do not connect drain to a close...

Страница 12: ...QUIRES A LARGER INSTALLATION SPACE THAN THE J TRAP 91P90 Figure 13 Typical Main and Overflow Drain Installations Inspecting and Replacing Filters IMPORTANT Filter access door must be in place during u...

Страница 13: ...iring must conform to the current National Electric Code ANSI NFPA No 70 or Canadian Electric Code Part I CSA Standard C22 1 and local building codes Refer to following wiring diagrams See unit namepl...

Страница 14: ...Page 14 Figure 14 CBX32MV Air Handler Unit Typical Wiring Diagram...

Страница 15: ...ROL PART NO 50W28 DISCHARGE SENSOR DAT TEMP RESISTANCE F OHMS 30 34 566 40 26 106 50 19 904 60 15 313 70 11 884 80 9 298 90 7 332 100 5 826 DETAIL A NOTE EVENHEAT MODE CANNOT BE ENABLED WITH HARMONY I...

Страница 16: ...DS DH G R Y1 W2 W1 R Y1 L C Heat Pump or Air Conditioner Control Y2 i W O i DS R C i i R C i i OUTDOOR UNIT THERMOSTAT R C i i Outdoor sensor for outdoor temperature display Optional OUTDOOR AIR SENSO...

Страница 17: ...NCE POINTS COMFORTSENSE T 7000 R R R W3 H W2 W2 W1 W1 W1 O O O L L Y1 Y1 Y1 Y2 Y2 G G C C C T T D B Y2 DS O D SENSOR X2658 Y2 OUT BL 1 1 CUT ON BOARD LINK R O CUT ON BOARD LINK R DS WHEN DEHUMIDIFICAT...

Страница 18: ...T 47W97 IS REQUIRED WHEN CONNECTING THE COMFORTSENSE 7000 CATALOG Y0349 WITH THE LSOM 2 RESISTOR KIT NOT REQUIRED WHEN USING COMFORTSENSE 7000 CATALOG Y2081 Figure 19 Control Field Wiring Cooling Appl...

Страница 19: ...P8 Position Function Description 1 Heat stage 1 relay coil 2 Heat stage 2 relay coil 3 Relay coil return 4 Heat stage 3 relay coil 5 Heat stage 4 relay coil 6 Heat stage 5 relay coil 7 L1 230VAC supp...

Страница 20: ...ED 1 2 3 4 1 2 3 4 1 2 3 4 COOLING HP MODE STANDARD HEAT MODE STAGED BY TSTAT STANDARD HEAT MODE DEFAULT 85 110 115 130 HEATING MODE BLOWER SPEED ELECTRIC HT MODE 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 LOW S...

Страница 21: ...in AUTO Humidification position H terminal is energized whenever indoor blower is running 2 EvenHeat Target Discharge Air Temperature selection is used to set discharge air temperatures for EvenHeat...

Страница 22: ...to stop DISPLAY An on board single character LED display see figure 21 for LED display location indicates general system status information such as mode of operation indoor blower CFM and error codes...

Страница 23: ...andler model size and capacity Blinking 1 When the correct Unit Sized Code is displayed RELEASE push button Selected code will flash for 10 second period 2 During ten second period HOLD push button un...

Страница 24: ...k wheel etc Indoor blower motor over temperature motor trip on internal protector Discharge air temperature sensor DATS out of range Restricted airflow Indoor blower motor is running at a reduced CFM...

Страница 25: ...580 1380 650 1545 730 NORM 1120 530 1215 575 1315 620 1400 660 975 460 1125 530 1275 600 1400 660 1010 475 1185 560 1200 565 1265 595 900 425 1000 470 1135 535 1265 595 CBX32MV 048 AND CBX32MV 060 BLO...

Страница 26: ...ow thermostat demand BASIC MODE Only active on a Y1 thermostat demand Normal Operation 1 On On On Acceptable 24 VAC High 100 ComfortSenset 7000 thermostat energizes Y1 and de energizes D on a call for...

Страница 27: ...set point Dehumidification call 2 On On On On Demand 0 VAC High 70 Dehumidification call ONLY 1 On On On On Demand 0 VAC High 70 ComfortSenset 7000 thermostat will keep outdoor unit energized after c...

Страница 28: ...l heating demands the indoor blower will run for an additional 10 seconds before de energizing No Yes NOTE If the call for lower heat section is removed AHC will automatically de energize higher heat...

Страница 29: ...number for each different air handler model for three seconds Yes No IMPORTANT Field replacement controls may need to be manually configured to validate air handler unit size code AIR HANDLER MODEL CB...

Страница 30: ...matically detect number of electric heat sections Electric heat section may be wired to energize more than one element 2 AHC waits for maximum of ten seconds to detect electric heat 22 volt DC relay c...

Страница 31: ...two Y1 and Y2 W1 and or W2 Heat Pump First and Second Stage First Electric Heat Section H1 Heat Pump First and Second Stage First Electric Heat Section Sec ond Electric Heat Section H2 if number of e...

Страница 32: ...Delay Timer Finished or last change was up stage Delay Timer Finished or last change was down stage Above Turn OFF Electric Heat Section Adjust Target Discharge Air Temperature Turn ON one Electric He...

Страница 33: ...and heat pump 2 Set Blower Adjust Selection jumper pin 3 Set Cooling Mode Blower Ramping jumper pin Cooling calls All ramping profiles are active Heating calls Only ramping profiles 1 and 2 are activ...

Страница 34: ...or blower per ramping profile No Yes AHC on board link must be cut between Y1 and Y2 to allow 2 stage cooling operation Air Handler Control AHC Indoor Blower Mode Speed and Profiles settings 1 Set Coo...

Страница 35: ...appears then release button To clear error codes stored in memory continue to hold push button while the solid three horizontal bars are displayed Release button when solid is displayed Solid c start...

Страница 36: ...e for servicing S Has an auxiliary pan been provided under the unit with separate drain for units installed above a finished ceiling or in any installation where condensate overflow could cause damage...

Страница 37: ...ue to fall the circuit between R and W1 is completed by the second stage heat room thermostat Circuit R W1 energizes a heat sequencer The completed circuit will energize supplemental electric heat if...

Страница 38: ...ide and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal corrosion and subsequently component failure REPAIRING DAMAGED INSULATION Areas...

Страница 39: ...Disposable filters should be replaced with a filter of the same type and size NOTE If you are unsure about the filter required for your system call your Lennox dealer for assistance 3 Reusable Filter...

Отзывы: